background image

 

 

 

                                           

 Programmable Controllers 

Rev 051115 

Ethernet Setup for the S2T 

 
Ethernet communications with the S2T CPU is done through the GEN651A Ethernet module.  
Prior to using this module, it must be configured using the EtherSetup_E setup software.  The 
EtherSetup_E software is used to configure the network parameters (IP Address, Subnet 
Mask, and Multicast Addresses) in the GEN651A Ethernet module.  When all the following 
setup steps described below are completed, Ethernet connection to the S2T through the 
GEN651A Ethernet module will be possible.   There are two methods of connection: 

 T-PDS (Toshiba Program Development Software). 

 UDP/IP Socket Interface.  

 

Setup GEN651 Ethernet Module 

This module must be setup 1

st

 before either of the connections methods are possible. 

1, Install the EtherSetup_E software on an MS Windows computer.  See the installation 
instructions in the User’s Guide for the Ethernet Module Parameter Setting Tool, 

6F8C1103.

 

 
2

 Set the network parameters in the GEN651A module. 

 

2.1  Set the DIP switches on the front of the EN6651A to enable setting the network 
parameters from the EtherSet_E.   Set DIP Switches 7 & 8 to ON (Note: 7 & 8 are the 

top 

two switches). 
 
2.2  Mount the EN651A on the S2T rack, then turn on power. 
 
2.3  Connect PC and EN6651A with the V-Tool cable (standard RS232C cross cable). 
 
2.4  Run the EtherSet_E software on the PC. 
 
2.5  Click the Read button on the EtherSetup_E screen. The current settings are read from 
the GEN651A and are displayed on the screen. 
 
 

On reading a module for the 
1

st

 time, settings will appear as 

shown to the left. 

 
 
 
 
 
 
 
 
 
 

Содержание S2T

Страница 1: ...his module must be setup 1st before either of the connections methods are possible 1 Install the EtherSetup_E software on an MS Windows computer See the installation instructions in the User s Guide for the Ethernet Module Parameter Setting Tool 6F8C1103 2 Set the network parameters in the GEN651A module 2 1 Set the DIP switches on the front of the EN6651A to enable setting the network parameters ...

Страница 2: ...651A Ethernet module If the EtherSetup_E can not establish communications with the GEN651A please make sure 1 The computer is connected directly to the GEN651A using as RS232 cross cable 2 The EtherSetup_E software is using the correct Com Port setting 3 No other computer software is running that uses the computer s RS232 port T PDS Setup In addition to setting up the Ethernet module network param...

Страница 3: ...ard alternate click on it and then click on Properties Note that the IP Address and Subnet Mast must be the same as set in T PDS the GEN651A the last digit of the IP Address must be different however it cannot be 1 The address of the GEN651A module is 172 16 64 1 Click OK In case of difficulty setting up the computer Ethernet card contact the company MIS IT Department ...

Страница 4: ...es the T PDS setup T PDS can now be connected to the S2E via Ethernet through the GEN651A Ethernet module Note If an attempt is made to assign an IP address in T PDS before the computer s Ethernet card is assigned a corresponding IP address then T PDS will return a Win Socket error This setting can also be made in the ladder logic with a MOV instruction ...

Страница 5: ...t is recommended that 2 UDP sockets be opened One for data send and one for data receive respectively 2 Execute UDP send and or UDP receive to exchange data via Ethernet 3 UDP socket close The instruction information on these functions is shown as follows UDP Socket Open SEND instruction is used A SEND B A H3100 fixed B Result status A 1 UDP open command H0031 B 1 Error code A 2 Socket number 1 to...

Страница 6: ...egister starting address Note 1 If receiver IP address is 192 0 0 5 HC0 0 0 5 set as follows A 3 H0005 A 4 HC000 Note 2 RW register 3 D register 4 Sample Program 12544 H3100 50 H0032 Socket number 1 Receiver IP address 192 0 0 5 16384 HC000 Receiver Port number 4000 Transmit ward size 200 Source data table is D1000 and after When R0622 is set to ON 200 data words D1000 to D1199 are transmitted to ...

Страница 7: ...e note 2 A 8 Destination data table register starting address A 9 Timeout setting 0 1s units see note 3 Note 1 If sender IP address is 192 0 0 5 HC0 0 0 5 set as follows A 3 H0005 A 4 HC000 For broadcast receiving set 0 0 0 0 Note 2 RW register 3 D register 4 Note 3 If A 9 0 there is no timeout Sample program 12544 H3100 51 H0033 Socket number 2 Sender IP address 192 0 0 5 16384 HC000 Sender Port ...

Страница 8: ... is finished R0621 is reset to OFF automatically UDP Socket Close SEND instruction is used A SEND B A H3100 fixed B Result status A 1 UDP close command H0034 B 1 Error code A 2 Socket number 1 to 12 Sample program 12544 H3100 52 H0034 Socket number 1 When R0623 is set to ON the UDP socket is closed When the operation is finished R0623 is reset to OFF automatically ...

Отзывы: