4. Programming
Menu Options
The MODE key accesses the three
primary modes of the S11 ASD; the
Standard Monitor Mode, the
Program Mode, and the Status
Monitor Mode. From any mode,
press the MODE key to loop through
to the other two modes.
The Standard Monitor Mode is used
to set and monitor the output
frequency of the ASD. Any active
Alarms or Faults will also be displayed here. The Program Mode is used to set the ASD
operating parameters. The Status Monitor Mode allows the user to monitor system
performance variables (i.e., output frequency, output current, terminal information, etc.).
Initial Parameter Programming
The operating parameters may be selected, viewed, or changed using the Operation Panel.
To change a setting press the MODE key to until the Program Mode menu is displayed. Use
the Up/Down arrow keys to scroll through the parameter listing. Select the item to be
changed and press the ENT key to enter the Edit mode. Set the parameter to the new value
using the Up/Down arrow keys. Press the ENT key to accept the change.
Press the MODE key while in the Edit mode to exit without saving the new value.
After setting the parameter, press the ENT key to display the programmed parameter or press
the MODE key to switch to the Status Monitor Mode.
For normal system operation the following parameters must be set by the user.
Extended Parameters
Extended Parameters provide quick access to ASD settings and can be selected, viewed, or
changed by performing the following:
1. Press the MODE key until the Program Mode screen is displayed.
2. Use the Up/Down arrow keys to scroll until the LED screen displays
F---
.
3. Press the ENT key to select.
4. Use the Up/Down arrow keys to scroll until the desired Extended Parameter has been
reached.
5. Press the ENT key to accept the change or press the MODE key while in the Edit mode to
exit without saving the new value.
LED Screen
Function
Selections
CMOD
Command Mode
0: Terminal Board
1: Operation Panel
FMOD
Frequency Command
0: Built-In Potentiometer
1: VIA
2: VIB
3: Operation Panel
4: Serial Communication
5: Up/Down from External Contact
6: VIA + VIB (Override)
ACC
Acceleration Time
0.0 – 3200 Seconds
DEC
Deceleration Time
0.0 – 3200 Seconds
UL
Upper Limit Frequency
0.5 –
FH
Hz (Set at parameter
FH
)
LL
Lower Limit Frequency
0.5 –
UL
Hz (Set at parameter
UL
)
PT
V/f Pattern
0: V/f Constant
1: Variable Torque
2: Automatic Torque Boost Control
3: Vector Control
4: Energy Saving
5: Dynamic Energy-Saving
6: PM Motor Control
THR
Motor Thermal Protection
10 – 100%
Additional Programming Information
Command Mode (Run Command)
The Command Mode selection establishes the primary source of the command input for the
ASD. The source of the Command control signal must be established for normal operation.
Commands are provided via the Terminal Board or the Operation Panel.
• The Terminal Board allows for Command control to be carried out via the Remote mode.
• The Operation Panel allows for Command control to be carried out via the Local mode.
For more information on the Local and Remote modes, see the Run section (section 5).
Frequency Command
Frequency Command controls the output speed of the ASD. The source
of the frequency control signal must be established for normal
operation.
The primary selections for the Frequency Command function are the
Built-In Potentiometer, VIA, VIB, or the Operation Panel.
The Built-In Potentiometer is the knob on the outside of the Operation Panel.
The VIA selection is an analog input terminal that accepts a 4-20 mA or 0–10 VDC signal
(configuration dependant). For a 4–20 mA signal place the VIA dip-switch in the I position.
For a 0–10 VDC signal place the VIA dip-switch in the V position. To scale the VIA input
terminal, program the following parameters as described.
4 – 20 mA Signal
F201 — 20%
F202 — 0 Hz
F203 — 100%
F204 — 60 Hz
The VIB selection is an analog input terminal that
accepts an external potentiometer signal and is
scaled by default.
The Operation Panel uses the Up/Down arrow
keys to provide the Frequency Command.
Default Terminal Settings
The default terminal settings may be changed by accessing the parameter via the Program
Mode.
Factory Default
Parameter settings may be returned to factory default values by performing the following:
1. Press the MODE key until the Program Mode screen is displayed.
2. Use the Up/Down arrow keys to scroll until the LED screen displays
typ
.
3. Press the ENT key to select.
4. Use the Up/Down arrow keys to scroll until the LED screen displays the number
3
on the
right side of the screen.
5. Press the ENT key to accept the change or press the MODE key while in the Edit mode to
exit without saving the new value. The LED screen will momentarily display
InIt
while
processing the reset. The LED screen will display the value
0
.
0
upon completion.
PP
VIA
VIB
CC
External
Potentiometer
-
+
4 – 20 mA
or 0 –10 VDC
Terminal
Default Function
RES
Reset
F
Forward Run
R
Reverse Run
S1
Preset Speed 1
S2
Preset Speed 2
S3
Preset Speed 3
PLC
Common
VIA
Frequency
VIB
Frequency
CC
Control Common
Control Circuit Input Terminals
Control Circuit Output Terminals
Terminal
Default Function
PP
Power Supply
FM
Output Frequency
P24
24 VDC Power Output
OUT
Speed Reach Signal
(Open Collector Output)
NO
FLA
Fault Relay Contact (N.O.)
FLB
Fault Relay Contact (N.C.)
FLC
Fault Relay Contact Common
RY
Low-Speed Signal
RC
Fr-F
MON
PRG
RUN
%
Hz
Status Monitor Mode
%
Hz
0.0
MON
PRG
RUN
Standard Monitor Mode
RUN
Program Mode
A H
U
MON
PRG
%
Hz
MODE
MODE
MODE
Menu Navigation
Basic Parameter Programming
VIA Dip-Switch