4. Programming

Menu Options

The MODE key accesses the three 

primary modes of the S11 ASD; the 

Standard Monitor Mode, the 

Program Mode, and the Status 

Monitor Mode. From any mode, 

press the MODE key to loop through 

to the other two modes.

The Standard Monitor Mode is used 
to set and monitor the output 

frequency of the ASD. Any active 

Alarms or Faults will also be displayed here. The Program Mode is used to set the ASD 
operating parameters. The Status Monitor Mode allows the user to monitor system 
performance variables (i.e., output frequency, output current, terminal information, etc.).

Initial Parameter Programming

The operating parameters may be selected, viewed, or changed using the Operation Panel. 

To change a setting press the MODE key to until the Program Mode menu is displayed. Use 
the Up/Down arrow keys to scroll through the parameter listing. Select the item to be 
changed and press the ENT key to enter the Edit mode. Set the parameter to the new value 
using the Up/Down arrow keys. Press the ENT key to accept the change. 

Press the MODE key while in the Edit mode to exit without saving the new value.

After setting the parameter, press the ENT key to display the programmed parameter or press 

the MODE key to switch to the Status Monitor Mode. 

For normal system operation the following parameters must be set by the user.

Extended Parameters

Extended Parameters provide quick access to ASD settings and can be selected, viewed, or 

changed by performing the following:

1.  Press the MODE key until the Program Mode screen is displayed.
2.  Use the Up/Down arrow keys to scroll until the LED screen displays 

F---

.

3.  Press the ENT key to select.
4.  Use the Up/Down arrow keys to scroll until the desired Extended Parameter has been 

reached.

5.  Press the ENT key to accept the change or press the MODE key while in the Edit mode to 

exit without saving the new value.

LED Screen

Function

Selections

CMOD

Command Mode

0:  Terminal Board
1:  Operation Panel

FMOD

Frequency Command

0:  Built-In Potentiometer
1:  VIA
2:  VIB
3:  Operation Panel
4:  Serial Communication
5:  Up/Down from External Contact
6:  VIA + VIB (Override)

ACC

Acceleration Time

0.0 – 3200 Seconds

DEC

Deceleration Time

0.0 – 3200 Seconds

UL

Upper Limit Frequency

0.5 – 

FH

 

Hz (Set at parameter 

FH

)

LL

Lower Limit Frequency

0.5 – 

UL

 

Hz (Set at parameter 

UL

)

PT

V/f Pattern

0:  V/f Constant

1:  Variable Torque

2:  Automatic Torque Boost Control

3:  Vector Control

4:  Energy Saving
5:  Dynamic Energy-Saving

6:  PM Motor Control

THR

Motor Thermal Protection

10 – 100%

Additional Programming Information

Command Mode (Run Command)

The Command Mode selection establishes the primary source of the command input for the 

ASD. The source of the Command control signal must be established for normal operation.
Commands are provided via the Terminal Board or the Operation Panel.

• The Terminal Board allows for Command control to be carried out via the Remote mode.
•  The Operation Panel allows for Command control to be carried out via the Local mode. 

For more information on the Local and Remote modes, see the Run section (section 5).

Frequency Command

Frequency Command controls the output speed of the ASD. The source 

of the frequency control signal must be established for normal 

operation. 

 The primary selections for the Frequency Command function are the 

Built-In Potentiometer, VIA, VIB, or the Operation Panel.

The Built-In Potentiometer is the knob on the outside of the Operation Panel.

The VIA selection is an analog input terminal that accepts a 4-20 mA or 0–10 VDC signal 
(configuration dependant). For a 4–20 mA signal place the VIA dip-switch in the I position. 
For a 0–10 VDC signal place the VIA dip-switch in the V position. To scale the VIA input 

terminal, program the following parameters as described. 
4 – 20 mA Signal 

F201 — 20%
F202 — 0 Hz
F203 — 100%
F204 — 60 Hz

The VIB selection is an analog input terminal that 
accepts an external potentiometer signal and is 
scaled by default.

The Operation Panel uses the Up/Down arrow 

keys to provide the Frequency Command.

Default Terminal Settings

The default terminal settings may be changed by accessing the parameter via the Program 
Mode.

Factory Default

Parameter settings may be returned to factory default values by performing the following:

1. Press the MODE key until the Program Mode screen is displayed.
2. Use the Up/Down arrow keys to scroll until the LED screen displays 

typ

.

3. Press the ENT key to select.
4. Use the Up/Down arrow keys to scroll until the LED screen displays the number 

3

 on the 

right side of the screen.

5.  Press the ENT key to accept the change or press the MODE key while in the Edit mode to 

exit without saving the new value. The LED screen will momentarily display 

InIt

 while 

processing the reset. The LED screen will display the value 

0

.

0

 upon completion. 

PP

VIA

VIB

CC

External

Potentiometer

-

+

4 – 20 mA 

or 0 –10 VDC

Terminal

Default Function

RES

Reset

F

Forward Run

R

Reverse Run

S1

Preset Speed 1

S2

Preset Speed 2

S3

Preset Speed 3

PLC

Common

VIA

Frequency

VIB

Frequency

CC

Control Common

Control Circuit Input Terminals

Control Circuit Output Terminals

Terminal

Default Function

PP

Power Supply

FM

Output Frequency

P24

24 VDC Power Output

OUT

Speed Reach Signal 

(Open Collector Output)

NO

FLA

Fault Relay Contact (N.O.)

FLB

Fault Relay Contact (N.C.)

FLC

Fault Relay Contact Common

RY

Low-Speed Signal 

RC

Fr-F

MON

PRG

RUN

%

Hz

Status Monitor Mode

%

Hz

0.0

MON

PRG

RUN

Standard Monitor Mode

RUN

Program Mode

A H

U

MON

PRG

%

Hz

MODE

MODE

MODE

Menu Navigation

Basic Parameter Programming

VIA Dip-Switch

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Содержание S11 ASD

Страница 1: ...d TIC products A A ddi ti onal i nf orm ati on can be f ound on our websi te Y ou m ay al so contact T I C f or addi ti onal i nf orm ati on by wri ti ng to 13131 W est L i ttl e Y ork R d Houston T exas 77041 vi a telephone at 713 466 0277 or via fax at 713 937 9349 Application Specific Q Who is considered qualified personnel A A qualified person is one who has the skills and knowledge about the ...

Страница 2: ...en moving the S11 ASD Contact your Toshiba Sales Representative to report discrepancies or for assistance if required 2 Mounting Only qualified personnel should install this equipment The installation of the equipment should conform to the 2008 National Electrical Code NEC Article 110 OSHA as well as any other applicable national regional or industry codes and standards Installation practices shal...

Страница 3: ...gnal must be established for normal operation Commands are provided via the TerminalBoard or the OperationPanel The TerminalBoardallows for Command control to be carried out via the Remotemode The Operation Panelallows for Command control to be carried out via the Local mode For more information on the Local and Remote modes see the Run section section 5 FrequencyCommand Frequency Commandcontrols ...

Страница 4: ...ng motor OC2 Over Current During Deceleration Deceleration time is too short Cooling fan is inoperative Ventilation openings are obstructed OC3 Over Current During Run Load fluctuations ASD is operating at an elevated temperature OCL Motor Over Current Motor insulation malfunction OFF ST Terminal is Of f Parameter F110 is improperly programmed OH Over Heat Cooling fan is inoperative Ventilations o...

Отзывы: