background image

Содержание RTM20

Страница 1: ...TOSHIBA TEMPERATURE CONTROL RELAY MODEL RTM20 ...

Страница 2: ...gs Engine exhaust Engine cylinders Furnaces Industrial processes RTD resistance temperature detector inputs are three compensated wire leads Adjustable trip point setting 40 C to 195 C Alarm outputs at 90 of trip temperature 12 mm display e Alarm sounds if sensors break Rugged compact case Selectable RTD materials ...

Страница 3: ...D s can be set at one trip temperature and the other two Table 1 Trip Temperature Channels Temperature indicator Power ON and OFF indicator Sensor disconnection or burnout indicator Temperature indicator set switch Manual reset switch RTD selection switches Reset mode selection switch manual or automatic can be set at another trip temperature In mode 2 three channels can be set at one trip tempera...

Страница 4: ... When that happens the trip indicator for either group A B or C will light up on the front of the relay Item Specification Temperature display range 20 to 200 C Frequency 50 60 Hz AC 100 to 120 V Supply voltage DC 100 to 125 V Power consumption 6 W Ambient Operation 10 to 60 C temperature Storage 20 to 70 C Trip setting 40 to 195 C range Outputs No of outputs 6 outputs 1 trip 1 alarm out puts for ...

Страница 5: ...TERMINAL BOARD RTD2 RTD4 RTD6 RTDS Drilling Plan 6 Y5 64 DIA HOLES 6 15 64 DIA HOLES 6 PLACES 4 PLACES 94 3 11 16 94 3 1 _ 16 104 4 3 32 J 3 32 Standard Installation with Installation M5 Bolts M5 Nuts are Provided on the Relay Unit mm in Unit mm in ALARM o o o o TRIP GROUP A ALARM o o o 0 TRIP GROUP B O 4 o O ALARM TRIP GROUP C o 0 o 0 ...

Страница 6: ...r information please contact your nearest Toshiba Liaison Representative or International Operations Producer Goods The data given in this catalog are subject to change without notice 98 7 A 70979 Toshiba International Corporation Houston Vancouver Toshiba International Corporation Pty Ltd Sydney Melbourne Toshiba International Europe Ltd Printed in Japan ...