– 14 –
• Work procedure 2
Applicable model:
Standard Duct type MMD-UP
1BH series,
Concealed Duct High Static Pressure type MMD-UP
1H series,
1-way Cassette SH type MMU-UP
1SH series,
Compact 4-way Cassette type MMU-UP
1MH series
<PMV Kit connection wiring method>
• To comply with the EMC (Electromagnetic Compatibility) standards, be sure to use the clamp filters that are
supplied accessories.
Clamp filter installation positions
• PMV Kit side:
A position 500 mm or less away from the shell of the PMV Kit body.
• Indoor unit side: A position between the PMV Kit body and the existing clamp filter and adjacent to the existing
clamp filter.
1) ~2) Perform the same process as 1) and 2) of Work procedure 1.
3) Be sure to install a clamp filter (accessory) on the PMV Kit side. The operation in this step is the same as the
operation in step 3) of Work procedure 1.
4) Open the electrical parts box cover of the indoor unit after power-off and then process wiring work.
For details, refer to the Installation Manual attached to the indoor unit.
5) Replace the PMV connector built in the indoor unit with the connection cable of PMV Kit.
The lock mechanism is provided at side of PMV connector. Remove the connector by releasing the lock
mechanism.
6) Be sure to install another clamp filter (accessory) on the indoor unit side. The operation in this step is the same
as the operation in step 3) of Work procedure 1.
7) The clamp filter (accessory) to be installed on the indoor unit side must be placed in the specified position as
shown in the picture (next page) and then the PMV Kit connection cable must be routed appropriately.
8) Fix the connection cable of PMV Kit with cord clamp for existing wiring.
NOTE
• Follow steps 6), 7), and 8) so that the portions of the cable before and after each of the clamp filters, including
the one already installed in the electrical parts box, do not come into contact with each other.
• When an air-conditioner is operated, with a clamp filter (accessories) not attached, it may become the
malfunction of an electronic device and the cause of failure in the circumference.
Connection
cable
Indoor unit
Clamp filter
(Accessory)
Clamp filter
(Already installed)
PMV Kit side
Indoor unit side
Clamp filter
(Accessory)
* After connecting to the P.C. board, install it adjacent to the existing clamp filter.
Pulse motor valve (PMV)
CN82
connector
PMV lead wires
Indoor control P.C. board
PMV
PMV Kit
500 mm or less
<Standard Duct type>
<Concealed Duct High Static Pressure type>
<1-way Cassette SH type>
Installation place for PMV
connector
(Blue, CN82)
P.C. board
<Connecting connection cable of PMV Kit.>
Remote controller wiring
Indoor / Outdoor control wiring
Cord clamp
* Fixed the connection cable of
PMV Kit
Power wiring
Clamp filter (Accessory)
Connection cable of PMV Kit
P.C. board
Wire clamp
* Pass the connection cable of PMV Kit
Power wiring
Clamp filter
(Accessory)
<Connecting connection cable of PMV Kit.>
Installation place for PMV connector
(Blue, CN82)
Connection cable of
PMV Kit
Cord clamp
* Fixed the
connection
cable of PMV Kit
Remote controller wiring
Indoor / Outdoor control wiring
27-EN
28-EN