13
EN
Branch Kit 1:3
Wiring Diagram
REQUIREMENT
•
The remote controller wiring has no polarity. Connections to terminals A and B of an
indoor unit may be replaced with each other.
•
The remote controller wires and power supply wire must not be in direct contact or in the
same conduit pipe. (Doing so may cause a malfunction of the control system due to
noise.)
Wiring Specification
Specification of Wires Between Units and Numbers of Wires.
Procure necessary parts and perform all connection work locally.
Outdoor unit - indoor unit
(header unit)
No. of wires
4 (Include ground wire)
Wire diameter
H07RN-F or 60245IEC66 1.5 mm
2
or more
Indoor unit
(header unit)
- indoor unit
(follower unit)
No. of wires
2
Wire diameter
H07RN-F or 60245IEC66 1.5 mm
2
or more
Remote controller wiring
No. of wires
2 (Shield wire)
Wire diameter
Between 0.5 mm
2
and 2 mm
2
(up to 200 m)
Grounding wire of indoor unit
H07RN-F or 60245IEC66 1.5 mm
2
or more
1
2
3
A
B
F
H
E
G
3
A
B
3
2
1
2
1
A
B
1
2
3
L
N
1
2
3
L1 L2 L3 N
H
H
Remote
Controller
Header
Indoor
Unit
Outdoor
Unit
Follower
Indoor
Unit
Power supply
Follower
Indoor
Unit
<RAV-SM1603AT-E>
<RAV-SM2244AT, SM2804AT series>
Power supply
Содержание RBC-TRP100E
Страница 25: ...EH99862001 a ...