background image

AIR CONDITIONER (SPLIT TYPE)

Installation

 Manual

Outdoor Unit

Model name:

<Heat Pump Model>

RAV-SP122AT2P-UL

RAV-SP182AT2P-UL

1131701101

For commercial use

Pour usage commercial

Para uso comercial

English

Installation Manual 

1

1131701101-00_S01_297x210_60p_S_p70_220426.indd   1

26/4/2565   11:41:08

Содержание RAV-SP122AT2P-UL

Страница 1: ...al Outdoor Unit Model name Heat Pump Model RAV SP122AT2P UL RAV SP182AT2P UL 1131701101 For commercial use Pour usage commercial Para uso comercial English Installation Manual 1 1131701101 00_S01_297x210_60p_S_p70_220426 indd 1 26 4 2565 11 41 08 ...

Страница 2: ... 14 13 Troubleshooting 17 14 Appendix 17 15 Specifications 18 1 EN 2 EN Original instruction Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the outdoor unit For installation of the indoor unit refer the Installation Manual attached to the indoor unit ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an...

Страница 3: ... Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Manufacturer He or she has been trained to install repair maintain relocate and remove the air conditioners made by Manufacturer or alternatively he or she has been instructed in such operations by an individual or individuals who have been trained an...

Страница 4: ...equipment observe precautions in the literature and on tags stickers and labels attached to the equipment Follow all safety codes Wear safety glasses and work gloves Keep quenching cloth and fire extinguisher nearby when brazing Use care in handling rigging and setting bulky equipment Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the ...

Страница 5: ...ty guards or by by passing any of the safety interlock switches Do not touch the intake or aluminium fins of the outdoor unit Doing so may result in injury Tighten the flare nut with a torque wrench in the specified manner Excessive tightening of the flare nut may cause a crack in the flare nut after a long period which may result in refrigerant leakage Install the air conditioner securely in a lo...

Страница 6: ...gerant pipe Disconnecting the refrigerant pipe with the service valve left open and with the compressor still operating will cause air etc to be sucked in raising the pressure inside the refrigeration cycle to an abnormally high level and possibly resulting in rupturing injury etc WARNING After installation work make sure below before operation Connection pipes are connected properly and no leakag...

Страница 7: ...unit and installation tools are different from those of the conventional refrigerant units Accordingly special tools are required for the new refrigerant R410A units For connecting pipes use new and clean piping materials with high pressure fittings made for R410A only so that water and or dust does not enter Required Tools Equipment and precautions for use Prepare the tools and equipment listed i...

Страница 8: ...ves on the gas and liquid sides 2 Pressurize the pipe with nitrogen gas charged from the service port to the design pressure 4 15 MPa to conduct an leakage test 3 Check for gas leaks using a leak tester for the HFC refrigerant 4 After the leakage test is completed evacuate the nitrogen gas Evacuation To evacuate system use a vacuum pump Do not use refrigerant charged in the outdoor unit for evacua...

Страница 9: ...ere the operating noise of the outdoor unit is transmitted When the outdoor unit is installed in an elevated position be sure to secure its feet A location in which drain water poses any problems When an outdoor unit is installed in a location that is always exposed to strong winds like a coast or on the high stories of a building one of the following is recommended Install the unit so that its di...

Страница 10: ...oundation for an outdoor unit with downward piping consider the piping work Absorb vibration with vibration proof rubber pads Fixing leg Correct Correct Foundation Foundation Foundation Bottom plate of outdoor unit Support the bottom surface of the fixing leg that is in contact with and underneath the bottom plate of the outdoor unit Incorrect Do not support the outdoor unit only with the fixing l...

Страница 11: ...eck for gas leaks at connected points Tightening of flare connections 1 Align the centers of the flare connections and fully tighten the flare nuts with your fingers Valve at liquid side 2 Use two wrenches to loosen or tighten the flare nut on the gas service valve as shown in the figure Use only one wrench to loosen or tighten the flare not on the liquid service valve The final tightening with a ...

Страница 12: ... Unit 500 microns Low side valve High side valve Vacuum pump Packed valve at gas side Charge port Valve core Setting pin Indoor Unit Service Valve High Side Refrigerant Low Side Charge hose Charge hose Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method...

Страница 13: ...ntil and the gauge of manifold dropped into the range of 0 5 0 kgf cm2 8 Use the Hexagon wrench to turning the valve rod of Gas side fully close And turn off the Air Conditioner system immediately thereafter 9 Remove the gauge manifold from the service port of the packed valve 10 Securely tighten the valve rod cap to the both service valves CAUTION Should be check the compressor operating conditio...

Страница 14: ...rconnections should be minimum 16 AWG Stripping length power cord and connecting wire Ground wire in mm Ground wire System interconnection wire Power supply wire How to wire 1 Remove the terminal cover by taking off the mounting screw 1 piece 2 Connect the power supply wires and system interconnection wires to the terminal block of the electrical control box 3 Tighten the screws of the terminal bl...

Страница 15: ...due to the high frequency wave generated by the frequency converter inverter in the outdoor unit If you touch the charged outdoor unit without a grounding wire you may experience an electric shock 9 Finishing After the refrigerant pipe inter unit wires and drain pipe have been connected make sure they are supported and fixed in place for the entire length Keep the power wires and system interconne...

Страница 16: ... the course of this operation hold down SW01 and SW02 simultaneously for at least 5 seconds to return to the initial status and then repeat the steps for recovering the refrigerant 29 EN 30 EN Refrigerant recovery When recovering the refrigerant in situations such as when relocating an indoor unit or outdoor unit the recovery operation can be performed by operating the SW01 and SW02 switches on th...

Страница 17: ...indicated when step 4 is taken D800 D801 D802 D803 D804 D805 ON OFF Slow flashing EN 31 EN 32 EN Existing piping The following settings are required when using a pipe Ø3 4 19 1 mm as the existing piping at the gas pipe side Steps taken to support existing piping 1 Set the circuit breaker to the ON position to turn on the power 2 Check that the LED displays are placed in their initial status If not...

Страница 18: ...he specified Pipe diameter and thickness be sure to use new pipes for the refrigerant piping works The operating pressure of R410A is high 1 6 times that of R22 and R407C If there is a scratch or dent on the pipe or a thinner pipe is used the pressure strength may be inadequate which may cause the pipe to break in the worst case Pipe diameter and thickness in mm Pipe outer diameter 1 4 6 4 3 8 9 5...

Страница 19: ...e the enclosed refrigerant label adjacent to the charging and or recovering location 2 Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink Then place the included transparent protective sheet over the label to prevent the writing from rubbing off 3 Prevent emission of the contained fluorinated greenhouse gas Ensure that the fluorinated greenhouse gas is neve...

Страница 20: ...s almost non existent If a conditioner system is to be installed in a small room select a suitable model and installation procedure so that if the refrigerant accidentally leaks out its concentration does not reach the limit and in the event of an emergency measures can be made before injury can occur In a room where the concentration may exceed the limit create an opening with adjacent rooms or i...

Страница 21: ...1131701101 1131701101 00_S01_297x210_60p_S_p70_220426 indd 59 26 4 2565 11 41 31 ...

Отзывы: