Error mode detected by outdoor unit
Operation of diagnostic function
Check code
Indoor unit
High Wall
F04
F06
F07
F08
F12
F13
F15
F31
H01
H02
H03
H04
L10
L29
Cause of operation
Disconnection, short of discharge
temp. sensor (TD)
Disconnection, short of outdoor temp.
sensor (TE)
Disconnection, short of outdoor temp.
sensor (TL)
Disconnection, short of outside temp.
sensor (TO)
Disconnection, short of suction temp.
sensor (TS)
Disconnection, short of heat sink temp.
sensor (TH)
Miss-mounting of outdoor temp. sensor
(TE, TS)
Outdoor P.C. EEPROM error
Compressor break down
∗
Although operation has started,
operation frequency decreases and
operation stops.
Compressor lock
∗
Over-current detection after
compressor start-up
Current detection circuit error
Case thermostat operation
∗
Abnormal overheat of compressor
Unset jumper of service P.C. board
Communication error between outdoor
P.C. board MCU
Status of
air conditioner
Stop
Stop
Stop
Continue
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Condition
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Judgment and measures
1. Check discharge temp. sensor (TD).
2. Check outdoor P.C. board.
1. Check temp. sensor (TE).
2. Check outdoor P.C. board.
1. Check temp. sensor (TL).
2. Check outdoor P.C. board.
1. Check outside temp. sensor (TO).
2. Check outdoor P.C. board.
1. Check suction temp. sensor (TS).
2. Check outdoor P.C. board.
1. Check outdoor P.C. board.
1. Check temp. sensor (TE, TS).
2. Check outdoor P.C. board.
1. Check outdoor P.C. board.
1. Check power supply voltage. (AC208V/230V ±10V)
2. Overload operation of refrigerating cycle
1. Trouble of compressor (Lock, etc.):
Replace compressor.
2. Wiring error of compressor (Open phase)
1. Check outdoor P.C. board.
(AC current detection circuit)
1. Check case thermostat and connector.
2. Check gas leak, recharge
3. Check full open of service valve.
4. Check PMV (Pulse Motor Valve).
5. Check broken pipe.
1. Outdoor service P.C. board
Check model type setting jumper wire.
1. Check outdoor P.C. board.
FILE NO. SVM-
12042
–