– 19 –
RAV-SM562MUT-E / RAV-SM562AT-E
∗
This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp
meter becomes 2 times of No. of compressor revolutions (rps).
Outdoor unit
Strainer
Packed valve
Outer dia. Ø12.7
Packed valve
Outer dia. Ø6.4
TS sensor
TD sensor
TO sensor
TE
sensor
Distributor
4-way valve
(STF-0108Z)
Muffler
Ø19 × L160
2-step muffler
Ø19 .05 × 200L
Rotary compressor
(DA150A1F-20F)
Heat exchanger Ø8 ripple,
2 rows, 14 steps
FP1.3 flat fin
PMV
(Pulse Motor Valve)
(CAM-B30YGTF-1)
R410A 1.0 kg
Cooling
Heating
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
Pressure
(MPa)
(kg/cm²G)
Pd
Ps
Pd
Ps
3.50
0.97
35.7
9.9
3.90
1.08
39.8
11.0
1.90
0.70
19.4
7.1
2.31
0.61
13.6
6.2
2.86
0.89
29.2
9.1
1.86
0.25
19.0
2.6
Pipe surface temperature (°C)
Discharge
Suction
Indoor heat Outdoor heat
exchanger
exchanger
(TD)
(TS)
(TC)
(TE)
85
14
12
48
93
26
17
54
48
7
5
30
87
5
40
1
86
17
47
11
69
–14
31
–15
Compressor
revolutions per
second (rps)
∗∗∗∗∗
70
70
50
97
95
98
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor
Outdoor
27/19
35/–
32/24
43/–
18/15.5
–5/–
20/–
7/6
28/–
24/18
15/–
–10/(70%)