Concealed Duct High Static Pressure
Installation Manual
EN
Duct design
1. In order to prevent short circuits, design the duct installation, so that the intake and discharge openings are not
adjacent to each other.
2. The indoor unit does not have a built-in air filter. Make sure to set up the filter chamber etc. and install the air filter (Locally
procured). If no air filter is installed, the heat exchanger will be blocked by dust, which may cause the malfunction of air
conditioner or the water leakage.
NOTE
All duct connection between units except outdoor unit must be procured and enforced locally.
Duct hose (with heat insulation)
Flexible duct hanging band
Air outlet chamber
(with heat insulation)
Air outlet port
connecting flange
Indoor unit
High efficiency filter
inserting port
Pre filter
inserting port
Air inlet port
connecting flange
Air inlet
chamber
Filter
chamber
Electrical control
box
from ground floor
Duct hose
Check port or carrying
in port (600x600)
Check port cap
Ceiling
Air outlet port
Air outlet port
to ground floor
<Duct installation example (First floor)>