– 53 –
7-2. Control Specifications
Cooling thermo. OFF (Fan)
• Setup air volume
Cooling
operation
Heating
operation
Ta
(˚C)
-1.0
Ts +
α
+1.0
No.
1
2
Item
When power
supply is reset
Operation
mode selection
Outline of specifications
1) Distinction of outdoor unit
When the power supply is reset, the outdoors are distinguished
and the control is selected according to the distinguished result.
1) Based on the operation mode selecting command from the
remote controller, the operation mode is selected.
Remote controller
command
STOP
FAN
COOL
HEAT
AUTO
Control outline
Air conditioner stops.
Fan operation
Cooling operation
Heating operation
• COOL/HEAT operation mode is
automatically selected by Ta, Ts and
To for operation.
• The operation is performed as shown
in the following figure according to Ta
value at the first time only.
(In the range of Ts +
α
–1 < Ta < Ts +
α
+ 1, Cooling thermo. OFF (Fan)/Setup
air volume operation continues.)
•
α
is corrected according to the outside temperature.
Remarks
Ta: Room temp.
Ts: Setup temp.
To: Outside temp.
k = deg
Outside temp.
No To
To ³ 24°C
24 > To ³ 18°C
To < 18°C
To error
Correction value (a)
0K
–1K
0K
+1K
0K