– 15 –
Concealed Duct High Static Pressure
Installation Manual
Connection of flexible hose
• Insert the soft socket of the attached flexible hose into the connecting port of the drain pipe until it
strikes against the end.
• Align the attached hose band to the end of the pipe connecting port, and then tighten it surely.
REQUIREMENT
• Be sure to fix the soft socket with the attached hose band and set the tightening position at upper side.
• Use the attached flexible hose by bending it with 45° or less so that no breakage or clogging occurs.
Connection of drain pipe
• Connect the hard socket (local supply) to the hard socket side of the attached flexible hose which has
been installed.
• Connect the drain pipes (local supply) successively to the connected the hard socket.
REQUIREMENT
• Using adhesive agent for vinyl chloride, connect the hard vinyl chloride pipes certainly so that water
does not leak.
• It requires several times to dry and harden the adhesive agent.
(Refer to Guide Manual of the adhesive agent.)
In this time, be sure not to apply force to the connecting section with the drain pipes.
Drain up
• When install the drain up kit of optional accessory, read the Installation Manual supplied to a drain up
kit.
Hose band
Flexible hose
Rising up (Trap)
15-EN