26
Procedure example
Manual address setup procedure
While the operation stops, change the setup.
(Be sure to stop the operation of the unit.)
Procedure
1
2
3
-1
3
-2
3
-3
4
-1
4
-2
4
-3
5
-1
5
-2
5
-3
Description
Push simultaneously
SET
+
CL
+
TEST
buttons for 4 seconds or more. After a while, the display part flashes as
shown below. Check the displayed CODE No. is [10].
• When the CODE No. is other than [10], push
TEST
button to
erase the display and repeat procedure from the first step.
(After pushing
TEST
button, operation of the remote controller
is not accepted for approx. 1 minute.)
(For a group control, No. of the firstly displayed indoor unit
(
∗
Display changes according
becomes the header unit.)
to the model No. of indoor unit.)
Every pushing
UNIT
LOUVER
button, the indoor unit No. in the group control is displayed in order.
Select the indoor unit of which setup is changed.
In this time, the position of the indoor unit of which setup is changed can be confirmed because fan of the
selected indoor unit operate.
Using temp. setup
/
buttons, specify
Indoor unit No. before setup change is displayed.
CODE No. [12]. (CODE No. [12]: Line address)
Using timer time
/
buttons, change the line address
from [3] to [2].
Push
SET
button.
In this time, the setup finishes when the display changes from
flashing to lighting.
Using temp. setup
/
buttons, specify
Indoor unit No. before setup change is displayed.
CODE No. [13]. (CODE No. [13]: Indoor address)
Using timer time
/
buttons, change the indoor address
from [3] to [2].
Push
SET
button.
In this time, the setup finishes when the display changes from
flashing to lighting.
Using temp. setup
/
buttons, specify
Indoor unit No. before setup change is displayed.
CODE No. [14]. (CODE No. [14]: Group address)
Using timer time
/
buttons, change the setup data from
[0001] to [0002].
(Setup data [Header unit: 0001] [Follower unit: 0002])
Push
SET
button.
In this time, the setup finishes when the display changes from
flashing to lighting.
1
7
2
,
6
7
3
-1,
4
-1,
5
-1,
6
3
-3,
4
-3,
5
-3
3
-2,
4
-2,
5
-2
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER