– 24 –
EN
Measures when a check code “E18” appears at the time of simultaneous
(twin, triple, or double twin) connection
1
Reconnect the wires between indoor unit and indoor unit correctly.
2
Change each indoor unit into correct address.
• Change the address of each indoor unit into correct one according to “Manual address setup procedure” in
the previous page when the check code “E18” appears on the remote controller.
4
Push the [
ON / OFF] button to start the
test mode. The screen
(1)
shown in the left
appears. (The screen
(2)
appears when the
operation is stopped.)
Perform the test mode in the “Cool” or “Heat”
mode.
Temperature setting cannot be adjusted during
the test mode.
Check codes are displayed as usual.
5
When the test mode is finished, push the
[
∧
] / [
∨
] button to select “1. Test
mode” on the “Field setting menu” screen,
then push the “
Set” [
F2]
button.
The screen
(3)
appears.
Pushing the “
Yes” [
F1] button
stops the test mode screen and continues the
normal operation.
NOTE
The test mode stops after 60 minutes and the screen
returns to the normal / detailed display.
Test
(1)
Room A
12:00
Mode
Fan Speed
Cool
Set
Yes
Test
(2)
Room A
12:00
Return
Test mode stop.
No
Yes
Test mode
(3)
A
1
2
3
B
1
2
3
A
1
2
3
B
A
1
2
3
B
1
2
3
A
1
2
3
B
Incorrect connection
Indoor unit
Outdoor unit
Remote
controller
Correct connection
Indoor unit
Outdoor unit
Remote
controller
Disconnect the
connection
③
-
③
between indoor units.
Monitor function
The sensor temperature or operational status of indoor unit, outdoor unit, or remote controller can be monitored.
1
Push the [
MENU] button to display the
menu screen.
2
Push and hold the [
MENU] button and
the [
∨
] button at the same time to
display the “Field setting menu”.
Push and hold the buttons for more than 4
seconds.
3
Push the [
∧
] / [
∨
] button to select
“4. Monitor function” on the “Field setting
menu” screen, then push the “
Set” [
F2] button.
Push the [
∧
] / [
∨
] button to select
the code to check data.
4
Push the [
CANCEL] button to return to
the “Field setting menu” screen.
*1 : Display and the contents
- - - - : Sensor function is not available.
0000 : Normal
0001 : Sensor has been used for 5 years.
0002 : Sensor trouble or exceeding the life of the
product for sensor
0003 : Sensor is detecting refrigerant leak
*2 : The above temperature values are estimated from
the temperature of the heat exchanger. It may differ
from the actual discharge temperature.
*3 : For outdoor unit data, refer to the Installation
Manual and Service Manual of the outdoor unit.
Monitor function
Code
01
Data
0024
Return
Set
Indoor unit data
Code
Data name
01
Room temperature (remote controller)
02
Indoor unit intake air temperature (TA)
03
Indoor unit heat exchanger (coil)
temperature (TCJ)
04
Indoor unit heat exchanger (coil)
temperature (TC)
07
Indoor unit fan speed (×1 rpm)
B9
Communication protocol
(0000: TCC-Link, 0001: TU2C-Link)
F3
Indoor unit fan cumulative operating hours
(×1 h)
E2
Indoor unit refrigerant leak detection sensor
output
*1
F8
Indoor unit discharge air temperature (TF)
*2
Outdoor unit data
*3
Code
Data name
60
Outdoor unit heat exchanger (coil)
temperature (TE)
61
Outside air temperature (TO)
62
Compressor discharge temperature (TD)
63
Compressor suction temperature (TS)
65
Heatsink temperature (THS)
6A
Operating current (×1/10)
6D
Outdoor heat exchange (coil)
temperature (TL)
F1
Compressor cumulative operating hours
(×100 h)
47-EN
48-EN
Содержание RAV-HM1101FT-TR
Страница 60: ...EB99848001 ...