– 17 –
9
Applicable controls
Basic procedure for changing
settings
Change the settings while the air conditioner is not
working.
(Stop the air conditioner before making
settings.)
CAUTION
Set only the CODE No. shown in the following table:
Do NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible
to operate the air conditioner or other trouble with
the product may result.
* The displays appearing during the setting process
differ from the ones for previous remote controllers
(AMT21E, AMT31E). (There are more CODE No.)
1
6
1
3
2
5
4
1
Push and hold button and “TEMP.”
button simultaneously for 4 seconds or
more. After a while, the display
fl
ashes as
shown in the
fi
gure. Con
fi
rm that the CODE
No. is [01].
y
If the CODE No. is not [01], push
button
to clear the display content, and repeat the
procedure from the beginning. (No operation of
the
remote controller is accepted for a while
after button is pushed.)
(While air conditioners are operated under the
group control, “ALL” is displayed
fi
rst. When
is pushed, the indoor unit number
displayed following “ALL” is the header unit.)
(* Display content varies with
the indoor unit model.)
REQUIREMENT
y
When you use this air conditioner for the
fi
rst
time, it takes approx. 5 minutes until the remote
controller becomes available after power-on. This
is normal.
<When power is turned on for the
fi
rst time
after installation>
It takes
approx. 5 minutes
until the remote
controller becomes available.
Power on
“SETTING”
fl
ashes
“SETTING”
goes out
Remote
controller is
available
Approx. 5 minutes
<When power is turned on for the second (or
later) time>
It takes
approx. 1 minute
until the remote
controller becomes available.
Power on
“SETTING”
fl
ashes
“SETTING”
goes out
Remote
controller is
available
Approx. 1 minutes
y
Normal settings were made when the indoor unit
was shipped from factory.
Change the indoor unit settings as required.
y
Use the wired remote controller to change the
settings.
* The settings cannot be changed using
the wireless remote controller, sub remote
controller, or remote-controller-less system
(for central remote controller only). Therefore,
install the wired remote controller to change the
settings.
2
Each time
button is pushed, indoor
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs and the louvers
start swinging. The indoor unit for change settings
can be con
fi
rmed.
3
Specify CODE No. [
] with “TEMP.”
/
buttons.
4
Select SET DATA [
] with “TIME”
/
buttons.
5
Push button. When the display changes
from
fl
ashing to lit, the setup is completed.
y
To change settings of another indoor unit, repeat
from Procedure
2
.
y
To change other settings of the selected indoor
unit, repeat from Procedure
3
.
Use button to clear the settings. To make
settings after button was pushed, repeat from
Procedure
2
.
6
When settings have been completed, push
button to determine the settings.
When button is pushed,
fl
ashes
and then the display content disappears
and the air conditioner enters the normal
stop mode.
(While
is
fl
ashing, no operation of the
remote controller is accepted.)
External static pressure
settings
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
procedure (
1
→
2
→
3
→
4
→
5
→
6
).
y
Specify [5d] to the CODE No. in procedure
3
.
y
For the SET DATA of procedure
4
, select a SET
DATA of the external static pressure to be set up
from the following table.
<Change on wired remote controller>
SET DATA
External static pressure
0000
40 Pa
Factory default
0001
30 Pa
0002
65 Pa
0003
50 Pa
0004
80 Pa
0005
100 Pa
0006
120 Pa
The list above is when SW501-1 and SW501-2 is OFF.
34-EN
33-EN
Содержание RAV-GM901BTP-E
Страница 29: ... 28 56 EN 55 EN ...