– 67 –
Table 2. Type: CODE No. 10
Table 3.
Indoor unit capacity: CODE No. 11
Setting data
0001
∗
1
0005
∗
2
Type
Type name abb.
Setting data
Type
4-way Cassette Type
Slim Duct Type
Disable
30
40
56
0000
∗
0003
0006
0009
RAV-GM
∗∗∗
UT
∗
RAV-RM
∗∗∗
SDT
∗
Table 4.
External static pressure settings CODE No.5d
Be sure to set up a tap change based upon the resistance (external static pressure) of the duct to be connected
.
The list above is when SW501-1 and SW501-2 is OFF.
* Include standard filter pressure loss.
Setup data
External static pressure
10Pa*
20Pa*
30Pa*
50Pa*
0000
0001
0003
0006
∗
1 EEPROM initial value on the P.C. board for indoor unit
servicing.
∗
2
CAUTION
For above models, set the CODE No. to “
CE
” and the
setting data “
0000
” (initial) to “
0001
”.
∗
EEPROM initial value on the P.C. board
for indoor unit servicing.
CODE No. (DN)
01
Item
Table 1. Setting data (CODE No. table (example))
Setting data
Factory-set value
Filter sign lighting time
Depending on Type
02
Filter pollution level
0000: standard
03
Central control address
0099: Not determined
06
Heating suction temperature shift
0002: +2 ˚C
0F
Cooling only
0000: Heat pump
10
Type
Depending on model type
11
Indoor unit capacity
Depending on capacity type
12
System address
0099: Not determined
13
Indoor unit address
0099: Not determined
14
Group address
0099: Not determined
8b
Connection of high heat feeling
0000: None
d1
Frost protection function
0000: None
28
Power failure automatic recovery
0000: None
5d
External static pressure
0000: 10Pa*
0001: 20Pa*
0003: 30Pa* (Factory default)
0006: 50Pa*
* Include standard filter pressure loss.
77
Dual set point
0000: Unavailable
31
Ventilation fan (standalone)
0000: Not available
32
Sensor SW (Selection of static pressure)
0000: Body sensor
60
Timer setting (wired remote controller)
0000: Available
d0
Remote controller operation save function
0001: Enable
2b
Thermostat output SW (T10
)
0000: Thermostat ON
1E
Temperature range of cooling/heating
automatic SW control point
0003: 3 deg (Ts ±1.5)
C2
Demand setting
(outdoor unit current demand)
0075: 75 %