background image

FILE No. A90-9612

SERVICE MANUAL

AIR CONDITIONER

              SPLIT TYPE

Printed in UK Dec  1996  s

2 WAY CASSETTE TYPE

RAV-133TU-PE/RAV-132A-PE

RAV-163TU-PE/RAV-182A-PE

Heronhill - for all your Toshiba requirements

Tel: 01823 665660

www.heronhill.co.uk

Fax: 01823 665807

Содержание RAV-132A-PE

Страница 1: ...MANUAL AIR CONDITIONER SPLIT TYPE Printed in UK Dec 1996 s 2 WAY CASSETTE TYPE RAV 133TU PE RAV 132A PE RAV 163TU PE RAV 182A PE Heronhill for all your Toshiba requirements Tel 01823 665660 www heronhill co uk Fax 01823 665807 ...

Страница 2: ...C Electromagnetic Compatibility and 73 23 EEC Low Voltage Operating conditions of units are as follows Note 1 Cooling Capacity is based on the following temperature conditions Indoor air inlet temperature 27 C DB 19 C WB Outdoor air inlet temperature 35 C DB Note 2 For details on the Remote Controller and Control Circuits refer to Service Manual A90 9504 OUTDOOR TEMPERATURE 2 TO 43 C ROOM TEMPERAT...

Страница 3: ...d tube Indoor fan type Transverse flow fan Air volume m3 h 700 Fan motor output W 7 x 2 Air filter Washable OUTDOOR UNIT Model RAV 132A PE Appearance colour Bronze white Munsell 6Y7 5 1 Dimensions Width mm Depth mm Height mm 740 880 310 Net weight kg 58 Ø 25 5 OD Outdoor fan type Propeller fan Air flow volume m3 h 2 700 Fan motor output W 39 PH230X3 4LS Compressor Model 1 5 Protective device Fuse ...

Страница 4: ...eller fan 2 700 39 Dimensions Height mm Width mm Depth mm Heat exchanger type Net weight Outdoor fan type Air flow volume Fan motor output Compressor Model Output A kg m3 h kW W Hz Bronze white Munsell 6Y7 5 1 740 INDOOR UNIT Model Smaller side size Coupler style Phase Indoor fan type Air volume OUTDOOR UNIT Model Appearance colour W m3 h Washable 1 45 1 220 240 60 RAV 182A PE PH250X3 4LS 1 5 Prot...

Страница 5: ...010 Panel outer dimension 1050 73 1 3 1 96 186 267 170 156 140 190 1050 840 130 480 190 Long hole Remote controller 600 Minimum Minimum 600 Minimum 70 70 Refrigerant piping joint Gas 12 7 Wiring connection 840 110 90 66 20 40 60 290 Hanger bolt 4 M10 Refrigerant piping joint Liquid 6 4 Drain pipe joint outer 25 5 25 600 A 12 5 83 5 2 4 5 x 9L 120 5 Heronhill for all your Toshiba requirements Tel 0...

Страница 6: ...ng Outlet Space for wiring and piping Space required for service When installed with the outlet faced to the wall side When installed with the inlet faced to the wall side Unit mm 4 12x18 slots Air outlet Both sides Carrying handle Electric parts box Terminal cover Refrigerant piping joint Knock out hole for drain Earth screw M6 Heronhill for all your Toshiba requirements Tel 01823 665660 www hero...

Страница 7: ... 3 1 RAV 133TU PE RAV 163TU PE 3 WIRING DIAGRAM Symbol Name Symbol Name FM Fan Motor 43 Relay RC Running Capacitor RY01 RY14 Relay TR Transformer SM01 02 Stepper Motor TA Sensor CS Float Switch TC Sensor DM Drain Motor F Fuse PCB F3 Fuse Interface PCB Heronhill for all your Toshiba requirements Tel 01823 665660 www heronhill co uk Fax 01823 665807 ...

Страница 8: ...Symbol RCc 51C 63F1 2 RCo F Do not operate the units with the magnetic contactor pushed in o shows terminal block and figures show terminal numbers Broken lines show wiring at site Symbol CM 52C FMo CH Surge Absorber WHI WHI BLK ORN ORN BLU BLU RED ORN BLU BLK BLK BLK RED WHI BLK RED Earth Screw Indoor Unit Outdoor Unit RED RED Heronhill for all your Toshiba requirements Tel 01823 665660 www heron...

Страница 9: ... 25 50 62 29 32 82 10 0 3 59 4 1RAV 133TU PE No PARTS NAME TYPE SPECIFICATIONS 1 Indoor unit fan motor x2 PAF 230 7 4 Output Rated 7W 4 pole 1 phase 230V 50Hz 2 Running capacitor for indoor fan motor x2 EEP2H105HQA105 AC 500V 1 0µF 3 Transformer Indoor unit ST 9586 AC187 264V 4 Stepper motor x2 MP35EA2 DC12V 80mNm 5 Relay LY2F AC 240V 2ab 6 Drain pump PCD 4N230TF 7 AC230V 0 2A 7 Float switch FS 08...

Страница 10: ...emp 165 C Resetting temp 80 C 4 3 RAV 132A PE 4 4 RAV 182A PE No PARTS NAME TYPE SPECIFICATIONS 1 Compressor PH250X3 4LS Output Rated 1 5kW 2 pole 220 240V 1 phase 50Hz 2 Outdoor unit fan motor SMF 230 39N 3 Output Rated 39W 6 pole 230V 1 phase 50Hz 3 Running capacitor for outdoor fan motor EEP2G405HQA114 AC400V 4µF 4 Magnetic contactor FMCA 1S AC 230V 50Hz 5 Pressure switch 2stage STB X602 Trippi...

Страница 11: ...as the Interface PCB is fitted to this unit to operate the dc stepper motors which drive the louvers The power supply to the interface PCB is via relay RY11 on the indoor PCB Heronhill for all your Toshiba requirements Tel 01823 665660 www heronhill co uk Fax 01823 665807 ...

Страница 12: ...ndenser Packed valve Refrigerant pipe Larger side ø 12 7 mm Refrigerant pipe Smaller side ø 6 4 mm Strainer Accumulator Pressure switch Outdoor Unit Indoor Unit Capillary IDø2 2 x 200L x 2P IDø1 7 x 300L x 2P Model RAV 132A PE RAV 182A PE Capillary IDø2 4 x 500L x1P IDø2 4 x 600L x 1P Evaporator Model RAV 133TU PE RAV 163TU PE Heronhill for all your Toshiba requirements Tel 01823 665660 www heronh...

Страница 13: ...acity Ratio Ambient Temp Dry Bulb o C Room Temp Wet Bulb o C 2 7 PERFORMANCE CHARACTER 7 1 Cooling capacity RAV 163TU PE RAV 182A PE 3 60 3 82 4 05 4 28 4 50 4 73 4 95 5 18 5 40 KW Heronhill for all your Toshiba requirements Tel 01823 665660 www heronhill co uk Fax 01823 665807 ...

Страница 14: ... at the installation site is unnecessary If the length of the pipe exceeds 20m add the refrigerant R 22 l Overcharge or undercharge of refrigerant in the outdoor unit will cause malfunction of the compressor The prescribed amount of the replenishment of the refrigerant is shown in the table above The permissible amount of refrigerant is the prescribed amount 50g Filled at factory 35 30 0 35 25 0 1...

Страница 15: ... Part No Description No 201 43A22001 Casing Assembly 202 43020288 Fan 203 43151217 Float Switch 204 43A70003 Pump Assembly 205 43020253 Bearing 206 43071019 Drain Connection 207 43070164 Drain Hose 208 43A60002 3 P Terminal 209 43A60001 4 P Terminal 210 43A21014 Fan Motor 211 43019604 Sensor Fix Plate 212 43A22002 Casing Outlet 213 43A44010 Heat Exchanger RAV 133TU PE 213 43A44012 Heat Exchanger R...

Страница 16: ... 4 43007107 Bushing 5 43007109 Plate connect short Location Part Description number Number 6 43009503 Grille L R 7 43007124 Support plate 8 43009499 ASM Grille Out 9 43A26001 ASM Motor 10 43007125 Support plate 2 5 5 2 4 7 7 4 6 7 4 10 5 3 1 1 4 8 2 8 9 2 Heronhill for all your Toshiba requirements Tel 01823 665660 www heronhill co uk Fax 01823 665807 ...

Страница 17: ...cation No 16 43155080 Capacitor Plastic Film 17 43162027 Cover Electric Parts 19 43145098 Dryer 20 43041837 Compressor PH230X3 4LS RAV132A PE 20 43041845 Compressor PH250X3 4LS RAV 182A PE 21 43148105 Accumulator 22 43146454 Packed Valve 1 4 IN 23 43146406 Packed Valve 1 2 IN 24 43A47013 CapillaryTube RAV132A PE 24 43146430 CapillaryTube RAV182A PE 25 43157167 Heater Crankcase 26 43193043 Spring P...

Страница 18: ... 89 Heronhill for all your Toshiba requirements Tel 01823 665660 www heronhill co uk Fax 01823 665807 ...