6. PERFORMANCE CHARACTERISTICS
Piping Length/Additional Refrigerant Volume
The amount of refrigerant put into the outdoor unit at the factory is sufficient to fill up to 20m of
refrigerant pipework.
If the length of the refrigerant pipework is 20m or less, addition of refrigerant at the installation site
is unnecessary.
If the length of the pipework exceeds 20m, extra refrigerant must be added. Refer to the table
below for details of the extra amounts.
Overcharge or undercharge of refrigerant in the outdoor unit will cause malfunction of
the compressor.
The prescribed amount of the replenishment of the refrigerant is shown in the table below:
!
!
!
!
ADD ONLY R407C REFRIGERANT TO THESE UNITS
!
6.5
134AH-PE
164AH-PE
134A-PE
164A-PE
0.18 0.35
—
—
—
—
0.79
1.05
1.23
1.4
—
—
—
—
0.18
0.35
—
—
—
—
0.94
1.2
1.38
1.55
—
—
—
—
0.18
0.35
—
—
—
—
0.79
1.05
1.23
1.4
—
—
—
—
0.18
0.35
—
—
—
—
0.94
1.2
1.38
1.55
—
—
—
—
MODEL
(RAV-)
Recharge amount if unit is reclaimed
(kg)
±
50g
Less
than
5m
Less
than
20m
Less
than
25m
Less
than
30m
Less
than
35m
Less
than
40m
Less
than
45m
Less
than
50m
Additional amount of refrigerant to add at
installation site (kg)
±
50g
Less
than
20m
Less
than
25m
Less
than
30m
Less
than
35m
Less
than
40m
Less
than
45m
Less
than
50m
Filled
at
Factory