– 6 –
• (
∗
) The RAS-B16GKVP-E cannot be used in combination with the RAS-M14GAV-E.
• For performance when each indoor unit is combined with other unit, refer to the separate table.
• The specifications may be subject to change without notice for purpose of improvement.
2-1. Specifications
<Heat Pump Models>
RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E / RAS-M14GAV-E, RAS-M18GAV-E
Unit model
Indoor
Outdoor
Cooling capacity
(kW)
Cooling capacity range
(kW)
Heating capacity
(kW)
Heating capacity range
(kW)
Power supply
Unit model
Indoor
Running current
(A)
(220V/230V/240V)
Power consumption
(W)
Power factor
(%)
Electric
Unit model
characteristics
Operation mode
Outdoor
Running current
(A)
(220V/230V/240V)
Power consumption
(W)
Power factor
(%)
Starting current
(A)
COP (Cooling/Heating)
Unit model
Indoor
High
(dB•A)
Operating
(Cooling/Heating)
Medium
(dB•A)
noise
Low
(dB•A)
Outdoor
Unit model
(Cooling/Heating)
2 indoor units operating (dB•A)
Unit model
Height
(mm)
Dimension
Width
(mm)
Indoor unit
Depth
(mm)
Net weight
(kg)
Fan motor output
(W)
Air flow rate
(Cooling/Heating)
(m³/h)
Unit model
Height
(mm)
Dimension
Width
(mm)
Depth
(mm)
Net weight
(kg)
Outdoor unit
Motor output
(W)
Compressor
Type
Model
Fan motor output
(W)
Air flow rate
(m³/h)
Type
Indoor unit
Unit model
Liquid side/Gas side
Outdoor unit
Unit model
Liquid side/Gas side
Piping
Maximum length (per unit)
(m)
Maximum length (total)
(m)
connection
Maximum chargeless length (total)
(m)
Maximum height difference
(m)
Additional refrigerant
Name of refrigerant
Weight
(kg)
Wiring
Power supply
connection
Interconnection
Usable
Indoor
(Cooling/Heating)
(°C)
temperature range
Outdoor
(Cooling/Heating)
(°C)
Unit model
Installation plate
Wireless remote controller
Batteries
Remote controller holder
Indoor unit
Zeolite-plus filter
Plasma pure filter
Accessory
Remote controller holder mounting screw
Owner’s manual
Mounting screw
Installation manual
Unit model
Installation manual
Outdoor unit
Specifications
Drain nipple
Water-proof rubber cap
RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E
RAS-M14GAV-E
RAS-M18GAV-E
4.0
5.2
1.4 – 4.5
1.4 – 6.2
4.4
6.7
0.9 – 5.2
0.9 – 8.5
220–240 V – 1 Ph – 50Hz / 220 V – 1 Ph –60Hz
RAS-B10GKVP-E
RAS-B13GKVP-E
RAS-B16GKVP-E (*)
0.15
0.15
0.15
30
30
30
91/87/83
91/87/83
91/87/83
RAS-M14GAV-E
RAS-M18GAV-E
Cooling
Heating
Cooling
Heating
4.87/4.64/4.44
4.43/4.23/4.04
7.12/6.80/6.50
8.28/7.91/7.57
1020
950
1540
1790
95
97
98
98
5.17/4.94/4.74
7.42/7.10/6.80
3.70/4.36
3.25/3.62
RAS-B10GKVP-E
RAS-B13GKVP-E
RAS-B16GKVP-E (*)
42/43
43/44
45/45
33/34
34/35
36/36
27/27
27/27
29/29
RAS-M14GAV-E
RAS-M18GAV-E
46/48
48/50
RAS-B10GKVP-E
RAS-B13GKVP-E
RAS-B16GKVP-E (*)
250
250
250
790
790
790
215
215
215
9
9
9
30
30
30
550/610
560/640
640/660
RAS-M14GAV-E
RAS-M18GAV-E
550
550
780
780
290
290
36
40
750
1100
Twin rotary type with DC-inverter variable speed control
DA111A1F-20F1
DA130A1F-25F
43
43
1820
2100
Flare connection
Flare connection
RAS-B10GKVP-E
RAS-B13GKVP-E
RAS-B16GKVP-E
Ø6.35/ Ø9.52
Ø6.35/ Ø9.52
Ø6.35/ Ø12.7
RAS-M14GAV-E
RAS-M18GAV-E
Ø6.35/ Ø9.52
Ø6.35/ Ø9.52
20
20
30
30
20
20
10
10
20g/m (pipe length 21m to 30m)
20g/m (pipe length 21m to 30m)
R410A
R410A
0.90
1.20
3 Wires : includes earth
4 Wires : includes earth
21 to 32/0 to 27
5 to 43/–10 to 24
RAS-B10GKVP-E
RAS-B13GKVP-E
RAS-B16GKVP-E
1
1
1
1
1
1
2
2
2
1
1
1
1
1
1
1
1
1
2 (Ø3.1 × 16L)
2 (Ø3.1 × 16L)
2 (Ø3.1 × 16L)
1
1
1
6 (Ø4 × 25L)
6 (Ø4 × 25L)
6 (Ø4 × 25L)
1
1
1
RAS-M14GAV-E
RAS-M18GAV-E
1
1
1
1
1
1
2
2