Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B.
WP-041
.
Defect
→
Replace.
Is connection of CN604
on P.C.B
WP-041
correct?
Is resistance value of TGa sensor correct?
Is connection of CN605
on P.C.B
WP-041
correct?
Is resistance value of TGb sensor correct?
Is connection of CN606
on P.C.B
WP-041
correct?
Is resistance value of TGc sensor correct?
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B.
WP-041
.
Defect
→
Replace.
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B.
WP-041
.
Defect
→
Replace.
YES
NO
YES
NO
YES
NO
Check
code
[1C]
(Continued)
Outdoor
LED display
z
zz
{
*
Check and troubleshooting
(Item without special mention indicates part of outdoor unit.)
[A room gas side temp. sensor (TGa) error]
[B room gas side temp. sensor (TGb) error]
[C room gas side temp. sensor (TGc) error]
{
:ON (
{
*:3 sec ON / 0.5 sec OFF)
z
:OFF
*
z
z
{
*
*
z
{
*
YES
NO
[Communication error
b
etween MCUs]
Are connections of CN802 on P.C.B MCC-
1
571
and CN80
2
on P.C.B
WP-041
correct?
Correct connection.
Check outdoor P.C. Boards.
Defect
→
Replace.
*
z
*
z
Are connections of CN802 on P.C.B
WP041
and CN802 on P.C.B MCC-1571 correct?
Are connections of CN804 on P.C.B
WP041
and CN800 on P.C.B MCC-1571 correct?
Correct connection.
Check outdoor P.C. Boards.
Defect
→
Replace.
Correct connection.
Check outdoor P.C. Boards.
Defect
→
Replace.
YES
YES
NO
NO
[Communication error between MCUs]
[Communication error between MCUs]
*
{
*
*
{
*
z
{
*
*
{
*
*
{
*
FILE NO. SVM-18051