background image

5

Outdoor Unit

Installation Manual

  

WARNING

•  Do not use any refrigerant different from the one speci

fi

 ed for complement or replacement. 

Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may 

result in a failure or explosion of the product or an injury to your body.

•  Installation work must be requested from the supplying retail dealership or professional vendors. 

Self-installation may cause water leakage, electrical shock, or 

fi

 re as a result of improper 

installation.

• Speci

fi

 ed tools and pipe parts for model R32 are required, and installation work must be 

done in accordance with the manual. HFC type refrigerant R32 has 1.6 times more pressure 
than that of conventional refrigerant (R22). Use the speci

fi

 ed pipe parts, and ensure correct 

installation, otherwise damage and/or injury may be caused. At the same time, water leakage, 
electrical shock, and 

fi

 re may occur.

•  Be sure to install the unit in a place which can suf

fi

 ciently bear its weight. If the load bearing of 

the unit is not enough, or installation of the unit is improper, the unit may fall and result in injury.

•  Electrical work must be performed by a quali

fi

 ed electrical engineer in accordance with the 

code governing such installation work, internal wiring regulations, and the manual. A dedicated 

circuit and the rated voltage must be used. Insuf

fi

 cient power supply or improper installation 

may cause electrical shock or 

fi

 re.

•  Use a cabtyre cable to connect wires in the indoor/outdoor units. Midway connection, stranded wire, 

and single-wire connections are not allowed. Improper connection or 

fi

 xing may cause a 

fi

 re.

•  Wiring between the indoor unit and outdoor units must be well shaped so that the cover can be 

fi

 rmly placed. Improper cover installation may cause increased heat, 

fi

 re, or electrical shock at 

the terminal area.

•  Be sure to use only approved accessories or the speci

fi

 ed parts. Failure to do so may cause 

the unit to fall, water leakage, 

fi

 re or electrical shock.

•  After the installation work, ensure that there is no leakage of refrigerant gas. If the refrigerant 

gas leaks out of the pipe into the room and is heated by 

fi

 re or something else from a fan heater, 

stove or gas range, it causes generation of poisonous gas.

•  Make sure the equipment is properly earthed. Do not connect the earth wire to a gas pipe, water 

pipe, lightning conductor, or telephone earth wire. Improper earth work may be the cause of 

electrical shock.

•  Do not install the unit where 

fl

 ammable gas may leak. If there is any gas leakage or accumulation 

around the unit, it can cause a 

fi

 re. 

•  Do not select a location for installation where there may be excessive water or humidity, such 

as a bathroom. Deterioration of insulation may cause electrical shock or 

fi

 re.

•  Installation work must be performed following the instructions in this installation manual. Improper 

installation may cause water leakage, electrical shock or 

fi

 re. Check the following items before 

operating the unit.

 

- Be sure that the pipe connection is well placed and there are no leaks.

 

- Check that the service valve is open. If the service valve is closed, it may cause 

overpressure and result in compressor damage. At the same time, if there is a leak in the 

connection part, it may cause air suction and overpressure, resulting in burst or injury.

•  The installation of pipe work shall be kept to a minimum.
•  The following must be certainly done during pump down.

•  Do not incorporate air into the refrigeration cycle.
•  Close the 2 service valves. Stop the compressor and remove the refrigerant pipe.
If the refrigerant pipe is removed when the compressor is operating and service valves are 
opened, the refrigerant cycle will inhale unwanted matter such as air and the pressure in the 
cycle becomes abnormally elevated. It may cause a burst or injury.

•  Do not modify the power cable, connect the cable midway, or use a multiple outlet extension 

cable. Doing so may cause contact failure, insulation failure, or excess current, resulting in 

fi

 re 

or electrical shock.

01_IM_1116791098_EN.indd   5

01_IM_1116791098_EN.indd   5

6/13/2561 BE   4:18 PM

6/13/2561 BE   4:18 PM

Содержание RAS-3M26U2AVG-E

Страница 1: ... RAS 4M27U2AVG E RAS 5M34U2AVG E NOTE Descriptions about operations for the E unit in this manual are not applicable to RAS 4M27U2AVG E Descriptions about operations for the D unit and the E unit in this manual are not applicable to RAS 3M26U2AVG E Installation Manual Outdoor Unit English R32 ...

Страница 2: ...ork 13 8 Grounding 14 9 Test run 14 10 Appendix 16 IMPORTANT NOTICE For details on how to install the indoor units refer to the installation manual accompanying the indoor units Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the outdoor unit For installation of the indoor unit refer to the Installation Manual at...

Страница 3: ...AL before operation Further information is available in the OWNER S MANUAL INSTALLATION MANUAL and the like Be sure to follow the precautions provided here to avoid safety risks The symbols and their meanings are shown below DANGER It indicates that incorrect use of this unit can result in a high possibility of severe injury 1 or death WARNING It indicates that incorrect use of this unit may cause...

Страница 4: ... SIZE TOOLS ARE ALSO REQUIRED FOR CONNECTING PIPES USE NEW AND CLEAN PIPING MATERIALS WITH HIGH PRESSURE WITHSTAND CAPABILITIES DESIGNED FOR R32 ONLY AND ENSURE THAT WATER OR DUST DOES NOT ENTER MOREOVER DO NOT USE ANY EXISTING PIPING AS ITS PRESSURE WITHSTAND MAY BE INSUFFICIENT AND MAY CONTAIN IMPURITIES DANGER THE MANUFACTURER SHALL NOT ASSUME ANY LIABILITY FOR THE DAMAGE CAUSED BY NOT OBSERVIN...

Страница 5: ...orinated greenhouse gases Do not vent gases to the atmosphere The appliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn refrigerant cycle parts Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer Be awa...

Страница 6: ...e to do so may cause the unit to fall water leakage fire or electrical shock After the installation work ensure that there is no leakage of refrigerant gas If the refrigerant gas leaks out of the pipe into the room and is heated by fire or something else from a fan heater stove or gas range it causes generation of poisonous gas Make sure the equipment is properly earthed Do not connect the earth w...

Страница 7: ...t in electric shock Do not store it in a wet basement or expose to rain or water After unpacking the unit examine it carefully for possible damage Do not install in a place that can increase the vibration of the unit Do not install in a place that can amplify the noise level of the unit or where noise and discharged air might disturb neighbours This appliance must be connected to the main power su...

Страница 8: ...or if the installation is not accepted by the supplier the service agency will take adequate countermeasures 7 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type R32 GWP 1 value 675 ex R32 ref AR4 1 GWP global warming potential The refrigerant quantity is indicated on the unit name plate Thi...

Страница 9: ...he combination of the indoor units which are operated The information in this specifications table applies for the combinations with the catalogue For operation read the owner s manual packed with the indoor unit Equipment complying with IEC 61000 3 12 1 If the air conditioner is used in conditions other than the above the safety protection functions may be activated Example of indoor unit class R...

Страница 10: ...or work is difficult you can change the procedure For example by making adjustments to the wiring and piping lengths on the inside rather than the outside When using an air conditioner under low outside temperature conditions Outside temp 5 C or lower In COOL mode prepare a duct or wind shield so that it is not affected by the wind Necessary Space for Installation If you need to install the outdoo...

Страница 11: ...KEEP IMPORTANT 6 POINTS FOR PIPING WORK 1 Take away dust and moisture inside of the connecting pipes 2 Tighten the connections between pipes and unit 3 Evacuate the air in the connecting pipes using a VACUUM PUMP 4 Check gas leak connected points 5 Be sure to fully open the packed valves before operation 6 Reusable mechanical connectors and flared joints are not allowed indoors When mechanical con...

Страница 12: ...cale with a precision of at least 10 g per index line when adding the refrigerant Do not use bathroom scales or similar instruments Use liquid refrigerant when refilling Since the refrigerant is in liquid form it can fill up quickly Therefore add the refrigerant gradually 7 Insulation of the Refrigerant Pipes Insulate the refrigerant pipes for liquid and gas separately Underground piping 10t Layin...

Страница 13: ...ime Then D805 light is flashing 5 times sec D800 D801 D802 D803 D804 D805 6 Hold down SW802 for at least 5 seconds Then outdoor unit start cooling mode The display is kept during the refrigerants collection operation D800 D801 D802 D803 D804 D805 7 Close the valve stem of the service valve at the liquid end 8 Make sure that the compound pressure gauge reading is 101 kPa 76 cmHg 9 Close the valve s...

Страница 14: ...les and has a contact separation of at least 3 mm must be incorporated into the fixed wiring 7 Wire Connection The dash lines show on site wiring 2 L N 3 1 2 3 2 L N 3 2 3 For indoor unit RAS M series For indoor unit RAS B series Main circuit Main circuit Input power Input power System interconnection wires System interconnection wires Leakage breaker Leakage breaker Remote controller Remote contr...

Страница 15: ...ty In the initial LED display status D805 is lighted as below ON OFF Rapid Flashing 5 times sec Slow Flashing 1 time sec D800 D801 D802 D803 D804 D805 Start running all the indoor units connected to the outdoor unit in the cooling mode The indoor unit in the room that doesn t operate the cooling mode cannot be checked 3 After 5 minutes hold down SW801 for at least 5 seconds and check that D800 is ...

Страница 16: ...ummer start running in the cooling mode first to decrease the temperature of the room then run in the heating mode Heating mode Set the temperature to 30 C If you perform the test run in winter start running in the heating mode first to increase the temperature of the room then run in the cooling mode Cooling mode Set the temperature to 17 C 2 For the test run be sure to satisfy the following cond...

Страница 17: ...al dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the following oil Mineral oil Suniso Freol S MS Synthetic oil alkyl benzene HAB Barrel freeze ester series PVE only of ether ser...

Страница 18: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1116791098 ...

Отзывы: