11-8-3. Indoor Unit (Other Parts)
11-8-4. Outdoor Unit
No.
1
Part name
Room temp. (TA) sensor
Heat exchanger (TC) sensor
Checking procedure
Disconnect the connector and measure the resistance value with tester.
(Normal temp.)
Temperature
Sensor
TA, TC (k
Ω
)
10°C
20°C
25°C
30°C
40°C
20.7
12.6
10.0
7.9
4.5
5
4
3
2
1
White
Yellow
Yellow
Yellow
Yellow
5
4
3
2
1
Refer to 11-5-1. (5).
Measure the resistance value of each winding coil by using the tester.
(Under normal temp. 25°C)
Position
1 to 2
1 to 3
1 to 4
1 to 5
Resistance value
2
0
0
Ω
± 7%
Refer to 11-5-1. (3) and (4).
2
3
Remote controller
Louver motor
24BYJ48-
A-080
4
Indoor fan motor
1
No.
Part name
Checking procedure
White
Red
Back
Measure the resistance value of each winding by using the tester.
Measure the resistance value of winding by using the tester.
Red
White
Black
Measure the resistance value of winding by using the tester.
Resistance value
145
0 ±
150
Ω
Under 2
0°C
Measure the resistance value of winding by using the tester.
COM
COM
2
5
4
Y
W
GR
BL
1
GR
6
O
3
Position
Gray - White
Gray - Orange
Gray- Yellow
Gray- Blue
Resistance value
42 to 50
Ω
42 to 50
Ω
42 to 50
Ω
42 to 50
Ω
Under 20°C
Position
Red - White
White - Black
Black- Red
Resistance value
16
to
51
Ω
2
3
4
Outdoor fan motor
(Model :
WDF-340-A43-1
)
4-way valve coil
(Model :
DXQ-939
)
Pulse modulating valve coil
Compressor
07k Series
Model :
NX66F0F-20D
10,13k Series
Model :
NX89F0F-20D
Under 20ºC
Position
Red - White
White - Black
Black - Red
Resistance value
NX66F0F-20D
NX89F0F-20D
3.19
Ω
3.36
Ω
(Model : PQ-M10012-000313)
FILE NO. SVM-16003
- 84 -