19
–
FILE NO. SVM-11015
7-2. Operation Data
<Cooling>
Tempeature
Model name
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
RAS-
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
27/19
35/-
10SKVP2-E
0.9 to 1.1
12 to 14
40 to 42
High
High
37
13SKVP2-E
0.8 to 1.0
8 to 10
41 to 43
High
High
58
16SKVP2-E
0.7 to 0.9
7 to 9
42 to 44
High
High
83
<Heating>
Tempeature
Model name
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
RAS-
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
20/-
7/6
10SKVP2-E
2.5 to 2.7
36 to 38
2 to 3
High
High
49
13SKVP2-E
2.7 to 2.9
40 to 42
2 to 3
High
High
65
16SKVP2-E 2.9 to 3.1 49 to 51 1 to 2 High High 83
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m