19
–
7-2. Operation Data
<Cooling>
Tempeature
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
27/19 35/- 0.9 to 1.1 12 to 14 37 to 39 High High 49
<Heating>
Tempeature
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
20/- 7/6 2.5 to 2.7 39 to 41 0 to 3 High High 60
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
FILE NO. SVM-10029