Work instructions

The existing R22 and R407C piping can be reused for 
inverter R410A product installations.

 

 

WARNING

Con

fi

rming the existence of scratches or dents on

the existing pipes and con

fi

rming the reliability of

the pipe strength are conventionally referred to the
local site.
If the speci

fi

ed conditions can be cleared, it is

possible to update existing R22 and R407C pipes
to those for R410A models.

Basic conditions needed to reuse existing
pipes

Check and observe the presence of three conditions in
the refrigerant piping works.
1. 

Dry

 (There is no moisture inside of the pipes.)

2. 

Clean

 (There is no dust inside of the pipes.)

3. 

Tight

 (There are no refrigerant leaks.)

Restrictions for use of existing pipes

In the following cases, the existing pipes should
not be reused as they are. Clean the existing pipes
or exchange them with new pipes.

1.  When a scratch or dent is heavy, be sure to use new 

pipes for the refrigerant piping works.

2.  When the existing pipe thickness is thinner than the 

speci

fi

ed “Pipe diameter and thickness,” be sure to 

use new pipes for the refrigerant piping works.

 

y

The operating pressure of R410A is high (1.6 times 
that of R22 and R407C). If there is a scratch or dent 
on the pipe or a thinner pipe is used, the pressure 
strength may be inadequate, which may cause the 
pipe to break in the worst case.

*  Pipe diameter and thickness (mm)

Pipe outer diameter

Ø6.4

Ø9.5

Ø12.7

Thickness

R410A

0.8

0.8

0.8

R22 (R407C)

 

y

In case the pipe diameter is Ø12.7 mm or less and 
the thickness is less than 0.7 mm, be sure to use new 
pipes for the refrigerant piping works.

3.  When the outdoor unit was left with the pipes 

disconnected, or the gas leaked from the pipes and 
the pipes were not repaired and re

fi

lled.

 

y

There is the possibility of rain water or air, including 
moisture, entering the pipe.

4.  When refrigerant cannot be recovered using a 

refrigerant recovery unit.

 

y

There is the possibility that a large quantity of dirty 
oil or moisture remains inside the pipes.

5.  When a commercially available dryer is attached to the 

existing pipes.

 

y

There is the possibility that copper green rust has 
been generated.

6.  When the existing air conditioner is removed after 

refrigerant has been recovered.

  Check if the oil is judged to be clearly different from 

normal oil.

 

y

The refrigerator oil is copper rust green in color:

  There is the possibility that moisture has mixed with 

the oil and rust has been generated inside the pipe.

 

y

There is discolored oil, a large quantity of residue, 
or a bad smell.

 

y

A large quantity of shiny metal dust or other wear 
residue can be seen in the refrigerant oil.

7.  When the air conditioner has a history of the 

compressor failing and being replaced.

 

y

When discolored oil, a large quantity of residue, 
shiny metal dust, or other wear residue or mixture of 
foreign matter is observed, trouble will occur.

8.  When temporary installation and removal of the air 

conditioner are repeated such as when leased etc.

9.  If the type of refrigerator oil of the existing air 

conditioner is other than the following oil (Mineral oil), 
Suniso, Freol-S, MS (Synthetic oil), alkyl benzene 
(HAB, Barrel-freeze), ester series, PVE only of ether 
series.

 

y

The winding-insulation of the compressor may 
deteriorate.

NOTE

The above descriptions are results have been con

fi

rmed 

by our company and represent our views on our air 
conditioners, but do not guarantee the use of the existing 
pipes of air conditioners that have adopted R410A in 
other companies.

Curing of pipes

When removing and opening the indoor or outdoor unit for 
a long time, cure the pipes as follows:

 

y

Otherwise rust may be generated when moisture or 
foreign matter due to condensation enters the pipes.

 

y

The rust cannot be removed by cleaning, and new 
pipes are necessary.

Placement 

location

Term

Curing manner

Outdoors

1 month or more

Pinching

Less than 1 month

Pinching or taping

Indoors

Every time

Are there scratches or dents on the existing pipes?

Is it possible to operate the existing air conditioner?

 

y

After the existing air conditioner is operated in cooling 
mode for approx. 30 minutes or longer,* recover the 
refrigerant.

 

y

For cleaning the pipes and recovering oil

 

y

Refrigerant recovery: Pump down method

 

y

Remove the existing air conditioner from the piping 
and carry out 

fl

ushing (nitrogen pressure 0.5 MPa) to 

remove any remains inside of the pipe.

Note:

  In case of twin pipes, also be sure to 

fl

ush the 

branching pipe.

Connect the indoor / outdoor units to the existing pipe.

 

y

Use a 

fl

are nut attached to the main unit for the indoor 

/ outdoor units. (Do not use the 

fl

are nut of the existing 

pipe.)

 

y

Re-machine the 

fl

are machining size to size for R410A.

 

y

(Airtight test), Vacuum dry, Refrigerant charge, Gas 
leak check

Test run

Was largely discolored oil or a large quantity 

of remains discharged? (When the oil deteriorates, 

the color of the oil changes to a muddy 

or black color.)

Existing pipes: Cannot be used.

 

y

Use new pipes.

Clean the pipes or use new pipes.

Piping necessary to change the 

fl

are nut / machining 

size due to pipe compression

1) Flare nut width: H

H

(mm)

Copper pipe 
outer diameter

Ø6.4

Ø9.5

Ø12.7

For R410A

17

22

26

For R22

Same as above

24

2) Flare machining size: A

A

(mm)

Copper pipe 
outer diameter

Ø6.4

Ø9.5

Ø12.7

For R410A

9.1

13.2

16.6

For R22

9.0

13.0

16.2

Becomes a little larger for R410A

Do not apply refrigerator oil to the 

fl

are surface.

(If there is discharge of remains, it is judged that a 
large quantity of remains are present.)

YES

YES

NO

NO

NO

YES

Nitrogen gas pressure 0.5 MPa

Содержание RAS-05, RAS-07

Страница 1: ...AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 1118350197 Indoor unit RAS 05 07 10 13 16BKV E Outdoor unit RAS 05 07 10 13 16BAV E ENGLISH ...

Страница 2: ... 4 Indoor Unit Fixing 5 Drainage 5 OUTDOOR UNIT 6 Installation Place 6 Precautions about Installation in Regions with Snowfall and Cold Temperatures 6 Refrigerant Piping Connection 6 Evacuating 7 ELECTRICAL WORKS 8 Wiring Connection 8 Power Supply and Connecting Cable Connection 9 Power Supply Input Wiring Diagram 10 OTHERS 11 Gas Leak Test 11 Remote Control A B Selection 11 Test Operation 11 Auto...

Страница 3: ...neighbors To avoid personal injury be careful when handling parts with sharp edges Please read this installation manual carefully before installing the unit It contains further important instructions for proper installation The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual Before installation please read these precautions for safe...

Страница 4: ... screw 6 6 Flat head wood screw 2 7 Owner s Manual 1 8 Installation Manual 1 Outdoor Unit No Part name No Part name 9 Drain nipple 1 Cap water proof 2 Not require to use for RAS 05 07 10 13BAV E Air filters Clean every 2 weeks 1 Open the air inlet grille 2 Remove the air filters 3 Vacuum or wash and then dry them 4 Reinstall the air filters and close the air inlet grille ...

Страница 5: ...it and wall and tilt the indoor unit for better operation For the rear left and left piping Wall Make sure to run the drain hose sloped downward Do not allow the drain hose to get slack Cut the piping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 6 mm thick heat ...

Страница 6: ...unit as shown in the diagram A place where there are no obstacles near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installed at least 2 5 m height Also it must be avoided to put anything on the top of the indoor unit CAUTION 5 4 45 5 7 Side view Top view Indoor unit R e ...

Страница 7: ... piping After scribing slits of the back body with a knife or a making off pin cut them with a pair of nippers or an equivalent tool In case of bottom right or bottom left piping After scribing slits of the back body with a knife or a making off pin cut them with a pair of nippers or an equivalent tool Slit Slit CAUTION Bind the auxiliary pipes two and connecting cable with facing tape tightly In ...

Страница 8: ...Drain the water from all the drain holes directly To protect the outdoor unit from snow accumulation install a holding frame and attach a snow protection hood and plate Do not use a double stacked design Precautions about Installation in Regions with Snowfall and Cold Temperatures Snow protection plate Snow protection hood Snow accumulation line Holding frame At least 50 cm Install at least 50 cm ...

Страница 9: ...dle of the gauge manifold valve 6 Open fully the valve stem of the packed valves both gas and liquid sides 7 Remove the charging hose from the service port 8 Securely tighten the caps on the packed valves Using a vacuum pump CAUTION KEEP IMPORTANT 5 POINTS FOR PIPING WORK 1 Take away dust and moisture inside of the connecting pipes 2 Tighten the connections between pipes and unit 3 Evacuate the ai...

Страница 10: ...tightly with screws 6 Tightening torque 1 2 N m 0 12 kgf m 7 Secure the connecting cable with the cord clamp 8 Fix the terminal cover and air inlet grille on the indoor unit Cord clamp Terminal cover Screw Screws Air inlet grille Front panel 1 Remove the valve cover the electric parts cover and the cord clamp from the outdoor unit 2 Connect the connecting cable to the terminal as identified by the...

Страница 11: ...ect to 1 2 3 Terminal block L N 1 2 3 Earth line Power supply cable Connecting cable Earth line Connecting cable Stripping length of the connecting cable 3 50 mm Earth line 10 mm 70 mm 10 mm Power Supply Input at Outdoor Unit Terminal Block Optional Indoor Unit Outdoor Unit Connecting cable connect to L 2 3 Terminal block L N 1 2 3 Earth line Connecting cable Connecting cable Stripping length of t...

Страница 12: ...urn out 8 Incorrect or incomplete wiring is carried out it will cause an ignition or smoke 9 This product can be connected to main power supply Connection to fixed wiring A switch which disconnects all poles and has a contact separation at least 3 mm must be incorporated in the fixed wiring Power supply input Wiring Diagram Power supply input at Indoor unit Terminal Block Recommend Indoor Terminal...

Страница 13: ...ating a unit two units may receive the remote control signal simultaneously and operate In this case the operation can be preserved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not received when the settings of indoor unit and remote control are different There is no relation between A setting B setting and A room B ro...

Страница 14: ...ner has a history of the compressor failing and being replaced y When discolored oil a large quantity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the fo...

Страница 15: ......

Страница 16: ...1118350197 ...

Отзывы: