
94
Q9 ASD Installation and Operation Manual
RX2 (AI1) Reference 2
Program
Frequency Settings
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode or the Torque Control mode.
This parameter sets the RX2 (AI1) input level that is associated with
when operating in the Speed control mode.
This value is entered as -100% to +100% of the RX2 (AI1) input signal range.
See RX2 (AI1) Reference 1 (
) for more information on this setting when
used for Speed control.
Direct Access Number — F224
Parameter Type — Numerical
Factory Default — +100
Changeable During Run — Yes
Minimum — -100
Maximum — +100
Units — %
RX2 (AI1) Frequency 2
Program
Frequency Settings
This parameter is used to set the gain and bias of the RX2 (AI1) input terminal
when the RX2 (AI1) terminal is used as the control input while operating in the
Speed Control mode.
This parameter sets
and is the frequency that is associated
when operating in the Speed Control
mode.
See RX2 (AI1) Reference 1 (
) for more information on this setting.
Direct Access Number — F225
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
Units — Hz
Содержание Q9 Series
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 217: ...Q9 ASD Installation and Operation Manual 207 Figure 28 See Table 13 and 14 for Actual Dimensions ...
Страница 218: ...208 Q9 ASD Installation and Operation Manual Figure 29 See Table 13 and 14 for Actual Dimensions ...
Страница 219: ...Q9 ASD Installation and Operation Manual 209 Figure 30 See Table 14 for Actual Dimensions ...
Страница 220: ...210 Q9 ASD Installation and Operation Manual Figure 31 See Table 13 and 14 for Actual Dimensions ...