46
Q7 ASD Installation and Operation Manual
Accel/Decel #1 Switching Frequency
Program
⇒
Fundamental #2
⇒
Acc/Dec #1 Pat
This parameter sets the frequency at which the acceleration/deceleration control
is switched from the Acc/Dec #1 profile to the Acc/Dec #2 profile during a
multiple-profile configuration.
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 80.0
Units — Hz
Accel/Decel #2 Pattern
Program
⇒
Fundamental #2
⇒
Acc/Dec #2 Pat
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the #2 Accel/Decel
parameter.
See
for more information on this parameter.
Settings:
S-Pattern 2
S-Pattern 1
Linear
Parameter Type — Numerical
Factory Default — Linear
Changeable During Run — No
Accel/Decel Display Resolution
Program
⇒
Utility Group
⇒
Acc/Dec Res
This parameter sets the number of decimal places to be displayed for Accel/
Decel functions.
Parameter Type — Numerical
Factory Default — 0.1
Changeable During Run — Yes
Minimum — 0.01
Maximum — 1
Adding Input Selection
Program
⇒
Protection
⇒
Adding Input Sel
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a modifier of the programmed Output Frequency.
Settings:
Pulse Input
Motorized Pot
Communication Card
RS232/485
Common Serial (TTL)
Binary/BCD Input
LED Keypad (option)
RX2 (option)
RX
RR
VI/II
Disabled
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No