E6581680

 

5.2. Transferring the configuration to an inverter 

 

This procedure allows the user to select the configuration file to be transferred to the inverter. 
 
The user must already have:   

 

-Loaded the inverter configuration file (

"*.CFG”

) onto the Parameter writer (see section 

5.1

OR  
-Generated the configuration file using PCM software and loaded this file onto the Parameter writer 
 

 

MLD -> Device

Filename1

MLD -> Device

Filename2

MLD -> Device

FilenameN

FilenameX

>>>>

FilenameX

>>>>>>>>

FilenameX

>>>>>>>>>>>>

Action Config

MLD -> Device

Main menu

Action

Store config

Successful

1

2

3

ENT

ENT

ENT

ENT

ENT

ENT

Action Config

XXXXXXXX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STEP 

Procedure 

• Turn the Parameter writer on using the ON/OFF button “F” (see section 3.2).  
• Connect the Parameter writer to the inverter using the RJ45 cable (see section 4.2).  
• Press “ENT” when the screen displays 

“Main menu / Action”

.  

• Press “ENT” when the screen displays 

“Action Config / MLD -> Device”

.  

• Select the file to be transferred using the arrow keys and press “ENT” to start the transfer. 

(see section 6.7). 

• The configuration has been transferred successfully from the Parameter writer. Disconnect 

the RJ45 cable from the inverter.   

• Pressing “ENT” returns the user to the 

“Action Config / MLD -> Device”

 menu. 

 
 Note 

:  

• Keep on pushing ESC key if the process of searching communication mode is canceled. 
• Display is changed faster by keeping on pushing      or      key. 

 

 

 
 
 

14 

Содержание PWU003Z

Страница 1: ...ivered to the end user of the inverter 2 Read this manual before first using the communications function and keep it handy as a reference for maintenance and inspections 3 All information contained in this manual are subject to change without notice Please confirm the latest information on our web site www inverter co jp ...

Страница 2: ...to injury 1 to people or that these errors may cause damage to physical property 2 1 Such things as injury burns or shock that will not require hospitalization or long periods of outpatient treatment 2 Physical property damage refers to wide ranging damage to assets and materials Meanings of symbols Marking Meaning of marking Indicates prohibition Don t do it What is prohibited will be described i...

Страница 3: ... fire For repairs call your sales repair agency Do not put any flammable material near the product It may catch fire due to the product sparking in the case of a malfunction Do not connect a LAN cable or telephone modular cable to Parameter writer Doing so may cause a failure or accident Electrical construction work must be done by a qualified expert Connection of input power by someone who does n...

Страница 4: ... produce noxious gases resulting in injury Persons who specialize in the processing of waste and known as Industrial Waste Product Collectors and Transporters or Industrial Waste Disposal Persons If the collection transport and disposal of industrial waste is done by someone who is not licensed for that job it is a punishable violation of the law Laws in regard to cleaning and processing of waste ...

Страница 5: ...ng the configuration to an inverter 14 5 3 Transferring the configuration to more than one inverter using Quick Store 15 6 PARAMETER WRITER MENUS 16 6 1 Parameter writer main menu 16 6 2 Action Load configuration from Parameter writer to inverter 17 6 3 Action Load configuration from inverter to Parameter writer 18 6 4 Quick Store mode 19 6 5 Supervision 20 6 6 Parameter settings Batteries 21 6 7 ...

Страница 6: ...ference 1 Receive and inspect the Parameter writer Check that the reference printed on the label is the same as that on the purchase order Remove the Parameter writer from its packaging and check that it has not been damaged in transit 2 Connect the Parameter writer see chapter 4 To a PC To an inverter 3 Copy inverter configurations see chapter 5 Load a configuration onto the Parameter writer Tran...

Страница 7: ...ter s SD card See the procedure on section 5 1 B The configuration file is generated by PCM software then transferred to the Parameter writer s SD card See the procedure on section 5 1 1 The user selects and then transfers the configuration file from the Parameter writer to the inverter See the procedure on section 5 2 2 Once the initial transfer is complete the user can use Quick Store mode which...

Страница 8: ...y note This should also correspond with the number on the purchase order Contents of the Parameter writer box PWU003Z Check that the Parameter writer box contains the following 1 Parameter writer 2 SD card 3 Standard USB type A to Mini B cable 4 RJ45 RJ45 RJ45 cable Length 1m 5 Carry case 6 User s manual Japanese and English 7 Impact resistant cover 8 Wrist strap 7 ...

Страница 9: ...E6581680 3 1 Presentation ENT ESC 65 181 5 27 4 TOSHIBA mm Figure 1 Approximate weight 250 g including batteries 8 ...

Страница 10: ...tory use only D SD card slot The SD card receives and stores the files One SD card is supplied with the Parameter writer E Battery compartment It can take 4 normal batteries and rechargeable batteries F Power ON OFF button Press for 2 seconds to turn the tool on or off G Quick Store key Press this key to transfer data from the Parameter writer to the inverter after an initial transfer in Quick sto...

Страница 11: ... OFF button See the display parameters menu on section 6 9 Connection to a powered up PC or inverter can also help conserve battery power as the power supply from the connected inverter takes over from the batteries Caution Do not use nickel cadmium rechargeable battery or manganese battery This may lead to liquid spill and fire Mandatory It is not possible occasionally to read according to the ki...

Страница 12: ...Parameter writer to avoid an incorrect start up of the PC The SD card must not be removed when the Parameter writer is on and a transfer is in progress Otherwise data on the SD card may be lost The file name length is 255 letters maximum The number of files that can be saved in the SD card is up to 65535 or less N B Too many files cause slow key operation response and display Number of files shoul...

Страница 13: ... cable from the inverter B 1 Remove all power from the inverter and all enclosures housing the inverter and wait more than 15 minutes and more to allow the DC bus of the inverter to discharge 2 Insert the Parameter writer s communication cable into the inverter s RJ45 communication port Refer to the inverter s installation manual for more information about how to perform this task 3 Install and cl...

Страница 14: ...T when the screen displays Main menu Action 1 Select the Action Config Device MLD menu using the arrow keys and press ENT Device MLD LoadFromDevicexx appears on the screen Press ENT until the transfer starts 2 Load Config Successful The configuration has been loaded successfully onto the Parameter writer disconnect the RJ45 cable from the inverter The inverter configuration file filexx CFG is now ...

Страница 15: ...T ENT Action Config XXXXXXXX STEP Procedure 1 Turn the Parameter writer on using the ON OFF button F see section 3 2 Connect the Parameter writer to the inverter using the RJ45 cable see section 4 2 Press ENT when the screen displays Main menu Action Press ENT when the screen displays Action Config MLD Device 2 Select the file to be transferred using the arrow keys and press ENT to start the trans...

Страница 16: ...reen displays Main menu Action Press ENT when the screen displays Action Config MLD Device 2 Select the file to be transferred using the arrow keys and press ENT to start the transfer If no inverter is connected a message No device connected appears on the screen see section 6 7 3 The configuration has been transferred successfully from the Parameter writer disconnect the RJ45 cable from the inver...

Страница 17: ...functions Load from Parameter writer to inverter Load from inverter to Parameter writer Main menu Device accesses the following information Device type Device version Main menu Parameters accesses Battery parameters Diagnostic parameters Password parameters Display parameters Main menu About MLD accesses Parameter writer version information The Quick Store key see section 3 2 allows the user to tr...

Страница 18: ...vice menu accessible from Main menu Action Action Config MLD Device This menu accesses the transfer function for loading configurations from the Parameter writer to the inverter Note Keep on pushing ESC key if the process of searching communication mode is canceled Display is changed faster by keeping on pushing or key 17 ...

Страница 19: ... MLD menu accessible from Main menu Action Action Config Device MLD This menu accesses the transfer function for loading configurations from the inverter to the Parameter writer Note Keep on pushing ESC key if the process of searching communication mode is canceled Display is changed faster by keeping on pushing or key 18 ...

Страница 20: ... 2 1 The diagram below shows the Quick Store mode which can be accessed after using either of the Action Config MLD Device menus Note 1 Quick Store mode can only be used after an initial transfer to an inverter has been completed Files can only be transferred between inverters with the same reference 19 ...

Страница 21: ...ain menu Device This supervisory menu is used to check the reference and version of the inverter connected to the Parameter writer Device Type This menu accesses the reference of the connected inverter Device SW version This menu accesses the software version of the connected inverter 20 ...

Страница 22: ...used to select the type of battery used by the Parameter writer normal batteries or rechargeable batteries Users must ensure that the correct battery type is selected so that the Parameter writer can accurately display the charge level This also affects message activation Battery Charge level Battery Alarm level Parameters Battery Alarm level 20 Save the level Charge level 78 Value between 0 and 5...

Страница 23: ... transfer to the inverter The inverter is in parameter change prohibition state Load config fault Incomplete or incorrect transfer from the Parameter writer to the inverter The inverter is in parameter read prohibition state Check the RJ45 cable and both of its connectors Make sure the connection is secure for the duration of the transfer Restart the transfer operation Confirm the inverter paramet...

Страница 24: ...lay Dis Display Contrast Set contrast 50 Save the contrast Display Backlight Set backlight 3 sec Save the backlight Set backlight 2 sec Display Sleep mode Set sleep mode 05 mn Save the sleep mode Display Language Language English Press and hold the up or down arrow key to define the contrast value more quickly Value between 0 and 100 Set contrast NN Press and hold the up or down arrow key to defin...

Страница 25: ...r future inverters 8 Warranty Any part of the unit that is proved to be defective will be repaired free of charge under the following conditions 1 This product will be repaired free of charge if problem fault occurs under normal handling within one year of delivery and is caused obviously by a design or manufacturing defect 2 The warranty applies only to the delivered unit 3 For the following kind...

Отзывы: