background image

 

ProtoNode Quick Install Guide – 66939-000 

 

 

Figure 6 

Step 7: Downloading Configuration File 

 

By default, the ProtoNode is setup with G9000 UPS Modbus configuration file.   If using a different UPS 

model, please go to 

http://www.toshiba.com/ind/product_display.jsp?id1=14&id2=30&id3=581

  and 

download the correct UPS protocol configuration file.  

 

1.

 

Before attempting to download the protocol configuration file onto the ProtoNode, put the 

protocol configuration file (e.g. config-mod.csv) in “Configuration File Folder”, by going to 

Start|Programs|FieldServerUtilities|Configuration File Folder. 

2.

 

From the main menu on RUI, type “d”, for the download configuration option. 

3.

 

Type “L” to specify the name and extension of the file to be sent to the ProtoNode (e.g. 

config-mod.csv). Hit <Enter> when done. 

4.

 

The utility will search for the configuration file specified on step 3 (e.g. config-mod.csv) to 

download the CSV  file  onto ProtoNode. On rare occasions where other files need to be 

downloaded to the ProtoNode, type ‘o’ for other files, then type “r” to specify the remote 

filename needed on the ProtoNode. 

5.

 

When satisfied that the correct file names are specified, type “d” to send the file to the 

ProtoNode. The utility will display progress until it is complete.  

6.

 

Note: Wait until the utility indicates that the download is complete before resetting the 

ProtoNode or you could corrupt the ProtoNode.

 

7.

 

Once download is complete hit <esc> key to go to the main menu. Type “!”  or cycle power 

to ProtoNode to put the new firmware into operation.  

8.

 

To verify that the protocol configuration file was downloaded successfully, go to the main 

menu and look on the top on the main menu to see the UPS model and the protocol (see 

figure 4). 

Note: If configuring multiple ProtoNode modules, see reference manual.  

Note: Make sure that you have the latest display, control board, and ProtoNode firmware 

versions installed. Failure to do so can cause  communications problems between the 

ProtoNode and UPS. 

 

Step 8: Testing and Commissioning of the ProtoNode 

 

1.

 

From the main menu of Remote User Interface, type “o”, for Connection Overview, to see 

the data traffic flow for each protocol. 

Содержание ProtoNode

Страница 1: ...que serial number and MAC address located on the underside of the unit These numbers should be recorded as they may be required for technical support Serial Number _________________________________________________ MAC Address __________________________________________________ 1 A DB 9 cable should be connected between the Serial 1 port on the ProtoNode and the serial port of the Toshiba UPS RS 232...

Страница 2: ...install NOTE These instructions assume a Windows Operating System Step 3 Identification of the ProtoNode on the Network 1 Check that the IP netmask of the PC matches the ProtoNode The default IP address of the ProtoNode is 192 168 1 168 and the default subnet mask is 255 255 255 0 see Section 10 2 in Reference manual to change the IP settings 2 Select Start Programs FieldServer Utilities Ping Util...

Страница 3: ... Ethernet adapter installed in the PC s Device Manager List and that it is configured to run the TCP IP protocol If using Windows XP ensure that the firewall is disabled If still having problems see Reference Manual Troubleshooting Tips Step 4 Connection to the ProtoNode Using RUI Remote User Interface 1 Open the Remote User Interface application by clicking Start Programs FieldServer Utilities Re...

Страница 4: ...nd then type the Netmask and hit the enter key when finished 4 Type 3 and then type the Gateway address and hit the enter key when finished 5 When done entering the information required hit the esc key and then type in order for the changes to take effect Step 6 Uploading New Firmware By default the ProtoNode is setup to work with ModBus Metasys and SNMP communication protocols If BACnet protocol ...

Страница 5: ...nload configuration to FieldServer menu See Figure 4 3 Type f for firmware and the program will automatically fetch the firmware from the Configuration File Folder See Figure 5 4 Type y for yes to precede the installation of the new firmware 5 Wait until the download completes Note resetting or turning off while the ProtoNode is installing the firmware can corrupt the ProtoNode 6 Once download is ...

Страница 6: ...nloaded to the ProtoNode type o for other files then type r to specify the remote filename needed on the ProtoNode 5 When satisfied that the correct file names are specified type d to send the file to the ProtoNode The utility will display progress until it is complete 6 Note Wait until the utility indicates that the download is complete before resetting the ProtoNode or you could corrupt the Prot...

Страница 7: ...Install Guide 66939 000 7 INDUSTRIAL DIVISION 13131 West Little York Rd Houston TX 77041 Tel 713 466 0277 Fax 713 466 8773 US 877 867 8773 Canada 800 872 2192 Mexico 01 800 527 1204 www toshiba com ind Printed in U S A ...

Страница 8: ...ProtoNode Quick Install Guide 66939 000 8 ...

Отзывы: