ProtoNode Quick Install Guide – 66939-000 

 

ProtoNode Quick Install Guide  

1.0  Introduction   

ProtoNode is a multi-protocol client/server device that is reliable to network serial and Ethernet devices.  
The ProtoNode works with SNMP, MODBUS RTU (Serial), MODBUS TCP, BACnet IP, BACnet MSTP(Serial), 
EtherNet/IP and Metasys N2. This Quick Install Guide provides the necessary information to set up and 
use the ProtoNode as quickly as possible.  

2.0  Package Components 

1.

 

Quick Install Guide 

2.

 

ProtoNode (Multi-Protocol Device Server)  

3.

 

One Cat5e direct Ethernet cable 

4.

 

One serial cable (Connection link between UPS and ProtoNode) 

5.

 

One power supply 

3.0  Installing the ProtoNode 

Step 1: Installation of the ProtoNode Hardware 

Each ProtoNode has a unique serial number and MAC address located on the underside of the unit. 

These numbers should be recorded as they may be required for technical support. 

 

Serial Number: _________________________________________________ 

 

MAC Address: __________________________________________________ 

 

1.

 

A DB-9 cable should be connected between the Serial 1 port on the ProtoNode and the 

serial port of the Toshiba UPS RS-232 port (See Figure 1).  NOTE: for G8000 UPS use a 

straight serial cable. Use a gender changer if needed. 

 

2.

 

Connect one end of the Ethernet cable to the ProtoNode RJ45 port and the other end to 
your computer (switch or Hub) RJ45 port. NOTE: The ProtoNode Ethernet port automatically 
senses an uplink connection, and may therefore be connected to a PC or a hub/switch using 
either a crossover cable (not supplied) or a direct Ethernet cable (supplied). 

3.

 

Connect the 5-30 VDC power supply adapter to the terminal block in the back of the 
ProtoNode. 

Содержание ProtoNode

Страница 1: ...que serial number and MAC address located on the underside of the unit These numbers should be recorded as they may be required for technical support Serial Number _________________________________________________ MAC Address __________________________________________________ 1 A DB 9 cable should be connected between the Serial 1 port on the ProtoNode and the serial port of the Toshiba UPS RS 232...

Страница 2: ...install NOTE These instructions assume a Windows Operating System Step 3 Identification of the ProtoNode on the Network 1 Check that the IP netmask of the PC matches the ProtoNode The default IP address of the ProtoNode is 192 168 1 168 and the default subnet mask is 255 255 255 0 see Section 10 2 in Reference manual to change the IP settings 2 Select Start Programs FieldServer Utilities Ping Util...

Страница 3: ... Ethernet adapter installed in the PC s Device Manager List and that it is configured to run the TCP IP protocol If using Windows XP ensure that the firewall is disabled If still having problems see Reference Manual Troubleshooting Tips Step 4 Connection to the ProtoNode Using RUI Remote User Interface 1 Open the Remote User Interface application by clicking Start Programs FieldServer Utilities Re...

Страница 4: ...nd then type the Netmask and hit the enter key when finished 4 Type 3 and then type the Gateway address and hit the enter key when finished 5 When done entering the information required hit the esc key and then type in order for the changes to take effect Step 6 Uploading New Firmware By default the ProtoNode is setup to work with ModBus Metasys and SNMP communication protocols If BACnet protocol ...

Страница 5: ...nload configuration to FieldServer menu See Figure 4 3 Type f for firmware and the program will automatically fetch the firmware from the Configuration File Folder See Figure 5 4 Type y for yes to precede the installation of the new firmware 5 Wait until the download completes Note resetting or turning off while the ProtoNode is installing the firmware can corrupt the ProtoNode 6 Once download is ...

Страница 6: ...nloaded to the ProtoNode type o for other files then type r to specify the remote filename needed on the ProtoNode 5 When satisfied that the correct file names are specified type d to send the file to the ProtoNode The utility will display progress until it is complete 6 Note Wait until the utility indicates that the download is complete before resetting the ProtoNode or you could corrupt the Prot...

Страница 7: ...Install Guide 66939 000 7 INDUSTRIAL DIVISION 13131 West Little York Rd Houston TX 77041 Tel 713 466 0277 Fax 713 466 8773 US 877 867 8773 Canada 800 872 2192 Mexico 01 800 527 1204 www toshiba com ind Printed in U S A ...

Страница 8: ...ProtoNode Quick Install Guide 66939 000 8 ...

Отзывы: