P9 ASD Installation and Operation Manual
139
Forward Run/Reverse Run Disable
Program
Frequency
Forward/Reverse Disable
This parameter
Enables/Disables
the
Forward Run
or
Reverse Run
mode.
If either direction is disabled, commands received for the disabled direction will
not be recognized.
If both directions are disabled, the received direction command will determine
the direction of the motor rotation.
Settings:
0 — Off
1 — Disable Reverse Run
2 — Disable Forward Run
Direct Access Number — F311
Parameter Type —
Selection List
Factory Default —
Off
Changeable During Run —
No
Random Mode
Program
Protection
Retry/Restart
This parameter adjusts the carrier frequency randomly. This feature is effective
in minimizing the negative effects of mechanical resonance.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F312
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Carrier Frequency Control Mode
Program
Special
Carrier Frequency
This parameter provides for the automatic decrease of the carrier frequency.
Select
1
to decrease the
Carrier Frequency
setting as a function of an
increased current requirement.
Selection
2
or
3
may also include an output voltage drop as a function of an
increased current requirement. The
Carrier Frequency
should be set below
4 kHz.
Settings:
0 — No Decrease and No Limit
1 — Valid Decrease and No Limit
2 — No Decrease and Limit Small Pulse
4 — Valid Decrease and Limit Small Pulse
Direct Access Number — F316
Parameter Type —
Selection List
Factory Default —
Valid Decrease and
No Limit
Changeable During Run —
Yes
Synchronized Deceleration Time
Program
Protection
Under-Voltage/Ridethrough
In the event that the
Ridethrough
function activates in a multiple-motor
application it will be necessary to manage the stopping motors synchronously
as not to damage the product being processed (e.g., wire spools, bobbin winder
for textile machines, etc.).
This parameter is used to minimize the product breakage during a momentary
power outage. This function stops multiple machines simultaneously or makes
them reach their respective command frequencies simultaneously by regulating
their deceleration times.
See
for additional information on this parameter.
Direct Access Number — F317
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......