Water piping
WARNING
• Install water pipes according to the regulations of respective
countries.
• Install water pipes in the freeze-free place.
• Make sure that water pipes have sufficient pressure resistance. The
design pressure is 1.0 MPa.
CAUTION
• Do not use zinc plated water pipes. When steel pipes are used,
insulate both ends of the pipes.
• Copper pipes are recommended.
• The water to be used must meet the water quality standard specified
in EN directive 98/83 EC.
Water piping and line heater installation
• Make the piping route a closed circuit. (An open water circuit may cause a failure.)
• Before a long period of none use, purge the water out of the pipes and thoroughly let them dry.
Do not add brine to the circulating water.
• Do not use the water used for the unit for drinking or food manufacturing.
• To insure easy maintenance, inspection, and replacement of the unit, use a proper joint, valve, etc (procured
locally) on the water inlet and outlet port.
• Be sure to install a strainer with 30 to 40 meshes (procured locally) on the water inlet pipe. If a strainer is not
installed, this may cause impaired performance, or damage to the plate heat exchanger from freezing.
• Install a suitable air vent (procured locally) on the water pipe. After sending water through the pipe, be sure to
vent the excess air.
• To avoid water leak, wrap some sealing tape around the screw part.
• Water pipes can get very hot, depending on the preset temperature. Wrap the water pipes with heat insulation
(procured locally) to prevent burns.
• Be sure to install the line heater (procured locally) on the water inlet side. In addition, position it within 5 m of the
water inlet pipe of the hot water module.
• Follow the table below to select a line heater (procured locally) within the range of 40 to 50 % of the hot water
module's rated capacity.
Hot water module model name
Capacity of line heater (kW)
MMW-AP0271LQ-E
3.2~4.0
MMW-AP0561LQ-E
6.4~8.0
Pipe size, material and insulator
The following specification for piping work and insulating process are procured locally.
Model MMW-
AP027
AP056
Connecting pipe
(unit side)
Water pipe
Inlet
R1-1/4
Outlet
R1-1/4
Connecting pipes material
Copper pipes are recommended
Insulator
Formed polyethylene foam, thickness: 10 mm or more
Water outlet R1-1/4
Air vent valve
Isolating Valve
Water inlet R1-1/4
Strainer
Crucial heater source
Pump
Line
Heater
29-EN
30-EN