– 3 –

SMMS 1-Way Cassette SH Type

Installation Manual

SMMS 1-Way Cassette SH Type

Installation Manual

1

Precautions for Safety

The manufacturer shall not assume any liability for the damage caused by not observing the description of this 
manual.

WARNING

General

• Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions 

to install the air conditioner.

• Only a qualified installer or service person is allowed to do installation work. Inappropriate installation may result in 

water leakage, electric shock or fire.

• Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally 

high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or 
an injury to your body.

• Before opening the intake grille of the indoor unit or service panel of the outdoor unit, set the circuit breaker to the 

OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with 
the interior parts. Only a qualified installer(*1) or qualified service person(*1) is allowed to remove the intake grille of 
the indoor unit or service panel of the outdoor unit and do the work required.

• Before carrying out the installation, maintenance, repair or removal work, set the circuit breaker to the OFF position. 

Otherwise, electric shocks may result.

• Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work 

is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.

• Only a qualified installer(*1) or qualified service person(*1) is allowed to undertake work at heights using a stand of 

50 cm or more or to remove the intake grille of the indoor unit to undertake work.

• Wear protective gloves and safety work clothing during installation, servicing and removal.
• Do not touch the aluminium fin of the unit. You may injure yourself if you do so. If the fin must be touched for some 

reason, first put on protective gloves and safety work clothing, and then proceed.

• Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor 

unit and result in injury.

• When work is performed at heights, use a ladder which complies with the ISO 14122 standard, and follow the 

procedure in the ladder’s instructions. Also wear a helmet for use in industry as protective gear to undertake the work.

• Before cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a 

“Work in progress” sign near the circuit breaker before proceeding with the work.

• Before working at heights, put a sign in place so that no-one will approach the work location, before proceeding with 

the work. Parts and other objects may fall from above, possibly injuring a person below. While carrying out the work, 
wear a helmet for protection from falling objects.

• The refrigerant used by this air conditioner is the R410A.
• The air conditioner must be transported in stable condition. If any part of the product is broken, contact the dealer.
• When the air conditioner must be transported by hand, carry it by two or more people.
• Do not move or repair any unit by yourself. There is high voltage inside the unit. You may get electric shock when 

removing the cover and main unit.

Selection of installation location

• When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration 

of refrigerant leakage occur in the room does not exceed the critical level.

• Do not install in a location where flammable gas leaks are possible. If the gas leak and accumulate around the unit, 

it may ignite and cause a fire.

• To transport the air conditioner, wear shoes with additional protective toe caps.
• To transport the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if 

the bands should break.

• Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive 

electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.

• Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise 

it may cause imperfect combustion.

Installation

• When the indoor unit is to be suspended, the designated hanging bolts (M10 or W3/8) and nuts (M10 or W3/8) must 

be used.

• Install the air conditioner securely in a location where the base can sustain the weight adequately. If the strength is 

not enough, the unit may fall down resulting in injury.

• Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may 

cause the product to fall down or topple over or give rise to noise, vibration, water leakage or other trouble.

• Carry out the specified installation work to guard against the possibility of high winds and earthquake. If the air 

conditioner is not installed appropriately, a unit may topple over or fall down, causing an accident.

• If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas 

comes in contact with fire, noxious gas may generate.

• Use forklift to carry in the air conditioner units and use winch or hoist at installation of them.

Refrigerant piping

• Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor 

is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is 
over pressurized, which may cause a injury.

• Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a 

crack in the flare nut after a long period, which may result in refrigerant leakage.

• After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows 

near a fire source, such as a cooking range, noxious gas may be generated.

• When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge 

the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge 
the air completely may cause the air conditioner to malfunction.

• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.

Electrical wiring

• Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air 

conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the 
work properly may result in electric shocks and / or electrical leaks.

• To connect the electrical wires, repair the electrical parts or undertake other electrical jobs, wear gloves to provide 

protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks. 
Failure to wear this protective gear may result in electric shocks.

• Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and 

laws. Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, 
smoking and / or a fire.

• Connect earth wire. (Grounding work) 

 

Incomplete grounding causes an electric shock.

• Do not connect earth wires to gas pipes, water pipes, and lightning conductor or telephone earth wires.
• After completing the repair or relocation work, check that the earth wires are connected properly.
• Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local 

regulations and laws.

• Install the circuit breaker where it can be easily accessed by the agent.
• When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
• Under no circumstances the power wire must not be extended. Connection trouble in the places where the wire is 

extended may give rise to smoking and / or a fire.

• Electrical wiring work shall be conducted according to law and regulation in the community and installation manual.

 

Failure to do so may result in electrocution or short circuit.

5-EN

6-EN

+00EH99880399_01EN.book  Page 3  Monday, April 4, 2011  11:24 AM

Содержание MMU-AP0154SH-E

Страница 1: ...on Manual English Indoor Unit Model name 1 Way Cassette Type MMU AP0154SH E MMU AP0184SH E MMU AP0244SH E AIR CONDITIONER MULTI TYPE Installation Manual 00EH99880399_01EN book Page 1 Monday April 4 2011 11 24 AM ...

Страница 2: ...involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such mat...

Страница 3: ...toe cap Repair of outdoor unit Gloves to provide protection for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You migh...

Страница 4: ... or receive electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation When the indoor unit is to be suspended the designated hanging bolts M10 or W3 8 and nuts M10 or W3 8 mu...

Страница 5: ... the refrigerant pipe Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be sucked in raising the pressure inside the refrigeration cycle to an abnormally high level and possibly resulting in rupture injury or other trouble CAUTION New Refrigerant Air Conditioner Installation This air conditioner adopts the new HFC ...

Страница 6: ...ment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditioner or noise may adversely affect the equipment s operation Locations where there is anything under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation from the indoor unit will drip possibl...

Страница 7: ...reless remote controller can be installed in the same room Model name MMU AP015 018 AP024 SET DATA Standard Factory defult 3 5 3 8 0000 High ceiling 1 4 0 4 0 0001 High ceiling 3 4 2 4 2 0003 A p p r o x 8 m 4 Installation CAUTION Strictly comply with the following rules to prevent damage of the indoor units and human injury Do not put a heavy article on the indoor unit or let a person get on it E...

Страница 8: ...isting angles or install new support angles Existing concrete slab Use a hole in anchors hole in plugs or a hole in bolts Rubber Anchor bolt Blade type bracket Slide type bracket Pipe hanging anchor bolt Hanging bolt Hanging bolt Support angle Installation of indoor unit Treatment of ceiling The ceiling differs according to structure of building For details consult your constructor or interior fin...

Страница 9: ...ite Flexible hose Use the attached flexible hose to adjust center discrepancy of the hard vinyl chloride pipe or to adjust the angle Do not use the flexible hose as stretched or do not deform it more extent than that in the following figure Fix the soft end of the flexible hose with the attached hose band Use the flexible hose on a horizontal level REQUIREMENT Perform heat insulation of the drain ...

Страница 10: ... chloride pipe To be local procure Drain pipe connecting port Hard socket VP25 vinyl chloride pipe To be local procure Attached hose band Attached flexible hose Soft socket Hard socket Socket for VP25 To be local procure VP25 vinyl chloride pipe To be local procure Indoor unit Indoor unit Rising up 696 mm or less Underside of ceiling Indoor unit 300 mm or less Rising up 850 mm or less When the ele...

Страница 11: ...ipe cutter Remove burrs completely Remaining burrs may cause gas leakage 2 Insert a flare nut into the pipe and flare the pipe Use the flare nut provided with the unit or the one used for the R410A refrigerant The flaring dimensions for R410A are different from the ones used for the conventional R22 refrigerant A new flare tool manufactured for use with the R410A refrigerant is recommended but the...

Страница 12: ...es Appliance shall be installed in accordance with national wiring regulations Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire CAUTION If incorrect incomplete wiring is carried out it will cause an electrical fire or smoke Install an earth leakage breaker that is not tripped by shock waves If an earth leakage breaker is not installed an electric ...

Страница 13: ...ore shield wire Wire size Up to 1000 m 1 25 mm Up to 2000 m 2 0 mm Remote controller wiring remote controller inter unit wiring Wire size 0 5 mm to 2 0 mm Total wire length of remote controller wiring and remote controller inter unit wiring L L1 L2 Ln In case of wired type only Up to 500 m In case of wireless type included Up to 400 m Total wire length of remote controller inter unit wiring L1 L2 ...

Страница 14: ...rol box Do not apply tension to the connecting section of the terminal block Mount the cover of the electrical control box without pinching wires Seal the wire connecting port with the attached heat insulator for sealing of wire connecting port Otherwise dewing may be caused R L S N U1 U2 A B Two screws Wire intake Electrical control box Cord clamp For power supply P C board Terminal block Wire in...

Страница 15: ...isplayed first When is pushed the indoor unit number displayed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan of the selected unit runs and the louvers start swinging The indoor unit for change settings can b...

Страница 16: ...H SET DATA Detection temperature shift value 0000 No shift 0001 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C SET DATA 0000 0001 Remotecontroller sensor Not used Factory default Used 9 Test Run Before test run Before turning on the power supply carry out the following procedure 1 By using 500 V megger check that resistance of 1 MΩ or more exists between the terminal block L to N...

Страница 17: ... 2 3 4 5 1 6 1 1 Always select HIGH air volume 10 Maintenance Daily maintenance Cleaning of air filter If is displayed on the remote controller maintain the air filter 1 Push the button to stop the operation then turn off the circuit breaker 2 Open the air intake grille Remove the screws of air intake grille fixing knob on a side of each filter Holding knobs of the air intake grille push the grill...

Страница 18: ...propriate measures when abnormal sound is generated Filter Indoor Dust dirt breakage Wash the filter with water when it is contaminated Replace it when it is damaged Fan Indoor Vibration balance Dust dirt appearance Replace the fan when vibration or balance is terrible Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them ...

Страница 19: ...controller E03 97 Communication error between indoor unit and remote controller Detected at indoor unit side Indoor unit E04 04 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received 04 Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detecte...

Страница 20: ... H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 1d Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 17 Current detect circuit system error IPDU H04 H04 44 Comp 1 case thermo operation I F H05 H05 TD1 sensor miswiring I F H06 H06 20 Low pressure protective operation I F H07 H07 d7 Oil level down detective protection I F H08 H08 01 TK1 sensor error 02 TK2 sensor er...

Страница 21: ...mp 2 side 03 Comp 3 side AF ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp I F P07 P07 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side IC ALT Heat sink overheat error IPDU I F P09 P09 Detected heat storage address 47 ALT No heat storage unit water error Heat storage unit P10 P10 Detected indoor unit addr...

Страница 22: ...1 Comp 2 Comp 3 Fan Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display AI NET central control display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending error in TCC LINK central control device TCC LINK C06 Receiving error in TCC LINK central control device TCC LINK C12 Bat...

Страница 23: ...holder Nick Ball Toshiba EMEA Engineering Director Toshiba Carrier UK Ltd Porsham Close Belliver Industrial Estate PLYMOUTH Devon PL6 7DB United Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMU AP0154SH E MMU AP0184SH E MMU AP0244SH E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditi...

Страница 24: ...in multi air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The s...

Страница 25: ...TANDARD 0000 F HIGH CEILING 1 0001 F HIGH CEILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE NO 01 F NO CHANGE F NONE 0000 F 150H 0001 F 2500H 0002 F 5000H 0003 F 10000H 0004 Filter sign lighting time CODE NO 0...

Страница 26: ...EH99880399 00EH99880399_01EN book Page 33 Monday April 4 2011 11 24 AM ...

Отзывы: