Toshiba
– 23 –
SMMS 4-way Air Discharge Cassette Type
Installation Manual
Procedure
2
Each time you push
button, indoor unit
numbers in the control group change cyclically.
Select the indoor unit you want to change settings
for.
The fan of the selected unit runs and the louvers
start swinging. You can confirm the indoor unit for
which you want to change settings.
Procedure
3
Using “TEMP.”
/
buttons, specify CODE
No. [
].
Procedure
4
Using timer “TIME”
/
buttons, select SET
DATA [
].
Procedure
5
Push
button. When the display changes from
flashing to lit, the setup is completed.
• To change settings of another indoor unit,
repeat from Procedure
2
.
• To change other settings of the selected indoor
unit, repeat from Procedure
3
.
Use
button to clear the settings.
To make settings after
button was pushed,
repeat from Procedure
2
.
Procedure
6
When settings have been completed, push
button to determine the settings.
When
button is pushed,
flashes and then
the display content disappears and the air
conditioner enters the normal stop mode.
(While
is flashing, no operation of the
remote controller is accepted.)
When installing separately
sold filters
Be sure to make ceiling setting when installing
separately sold filters.
* Separately sold filters cannot be installed in an
indoor unit on a high ceiling.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No. in Procedure
3
, specify [5d].
• For the SET DATA in Procedure
4
, select the
SET DATA of filters to be installed from the
following table.
Installing indoor unit on
high ceiling
When an indoor unit is installed on a ceiling higher
than the standard height, make the high-ceiling
setting for air volume adjustment.
• Take the same procedure as that in “When
installing separately sold filters”.
• For the CODE No. in Procedure
3
, specify [5d].
• Select the SET DATA for Procedure
4
from the
“Height list of ceiling possible to be installed”
table on page 7 in this manual.
SETTING
SETTING
SET DATA
High-ceiling setting
0000
Normal filter
(Factory setting)
SET DATA
High-ceiling setting
0003
High Efficiency Filter (65%)
High Efficiency Filter (90%)
23-EN
+00EH99863501_6L_SMMS_4-way_IM1_printOnly.book Page 23 Thursday, September 11, 2008 9:29 AM