SMMS 2-way Air Discharge Cassette Type
Installation Manual
EN-61
EN-62
E20
E20
01:
Outdoor unit of other line connected
02:
Indoor unit of other line connected
Other line connected during automatic address
I/F
E21
E21
02:
No header unit
00:
Multiple number of header units
Error in number of heat storage master units
I/F
E22
E22
—
Reduction in number of heat storage units
I/F
E23
E23
—
Sending error in communication between outdoor units
Error in number of heat storage units (trouble with reception)
I/F
E25
E25
—
Duplicated follower outdoor addresses
I/F
E26
E26
No. of outdoor units which received signal
normally
Decrease of No. of connected outdoor units
I/F
E28
E28
Detected outdoor unit number
Follower outdoor unit error
I/F
E31
E31
Number of IPDU (*1)
IPDU communication error
I/F
F01
—
—
ALT
Indoor unit TCJ sensor error
Indoor unit
F02
—
—
ALT
Indoor unit TC2 sensor error
Indoor unit
F03
—
—
ALT
Indoor unit TC1 sensor error
Indoor unit
F04
F04
—
ALT
TD1 sensor error
I/F
F05
F05
—
ALT
TD2 sensor error
I/F
F06
F06
01:
TE1 sensor
02:
TE2 sensor
ALT
TE1 sensor error
TE2 sensor error
I/F
F07
F07
—
ALT
TL sensor error
I/F
F08
F08
—
ALT
TO sensor error
I/F
F10
—
—
ALT
Indoor unit TA sensor error
Indoor unit
F12
F12
—
ALT
TS1 sensor error
I/F
F13
F13
01:
Comp. 1 side
02:
Comp. 2 side
03:
Comp. 3 side
ALT
TH sensor error
IPDU
F15
F15
—
ALT
Outdoor unit temp. sensor miscabling (TE, TL)
I/F
F16
F16
—
ALT
Outdoor unit pressure sensor miscabling (Pd, Ps)
I/F
F22
F22
—
ALT
TD3 sensor error
I/F
F23
F23
—
ALT
Ps sensor error
I/F
F24
F24
—
ALT
Pd sensor error
I/F
F29
—
—
SIM
Indoor unit other error
Indoor unit
F31
F31
—
SIM
Indoor unit EEPROM error
I/F
Check code
Wireless remote controller
Check code name
Judging device
Wired remote
controller display
Outdoor unit 7-segment display
Sensor block display of receiving unit
Auxiliary code
Operation
Timer
Ready
Flash