GR
NL
PT
ES
IT
DE
FR
RU
SI
SK
LV
CS
TR
EN
27-EN
–27–
Toshiba 1112750201 (EN)
Installation Manual
L03
—
—
SIM
Indoor centre unit duplicated
Indoor
L04
L04
—
SIM
Outdoor line address duplicated
I/F
L05
—
—
SIM
Duplicated indoor units with priority
(Displayed in indoor unit with priority)
I/F
L06
L06 No. of indoor units with priority
SIM
Duplicated indoor units with priority
(Displayed in unit other than indoor
unit with priority)
I/F
L07
—
—
SIM
Group line in individual indoor unit
Indoor
L08
L08
—
SIM
Indoor group/Address unset
Indoor / I/F
L09
—
—
SIM
Indoor capacity unset
Indoor
L10
L10
—
SIM
Outdoor capacity unset
I/F
L17
—
—
SIM
Outdoor unit type mismatch error
I/F
L20
—
—
SIM
Duplicated central control addresses
AI-NET,
Indoor
L26
L26
Number of heat storage units
connected
SIM
Too many heat storage units
connected
I/F
L27
L27
Number of heat storage units
connected
SIM
Error in number of heat storage units
connected
I/F
L28
L28
—
SIM
Over No. of connected outdoor units
I/F
L29
L29 Number of IPDU (*1)
SIM
No. of IPDU error
I/F
L30
L30 Detected indoor address
SIM
Indoor outside interlock
Indoor
—
L31
—
—
Extended I/C error
I/F
P01
—
—
ALT
Indoor fan motor error
Indoor
P03
P03
—
ALT
Discharge temp. TD1 error
I/F
P04
P04
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT
High-pressure SW system operation
IPDU
P05
P05
00:
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT
Phase missing detection/Power failure
detection
Inverter DC voltage error (comp.)
Inverter DC voltage error (comp.)
Inverter DC voltage error (comp.)
I/F
P07
P07
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT
Heat sink overheat error
IPDU, I/F
P09
P09
Detected heat storage
address
ALT
No heat storage unit water error
Heat storage
unit
P10
P10 Detected indoor address
ALT
Indoor overfl ow error
Indoor
P12
—
—
ALT
Indoor fan motor error
Indoor
P13
P13
—
ALT
Outdoor liquid back detection error
I/F
P15
P15
01: TS condition
02: TD condition
ALT
Gas leak detection
I/F
P17
P17
—
ALT
Discharge temp. TD2 error
I/F
P18
P18
—
ALT
Discharge temp. TD3 error
I/F
P19
P19 Detected outdoor unit number
ALT
4-way valve inverse error
I/F
P20
P20
—
ALT
High-pressure protective operation
I/F
P22
P22
0*: IGBT circuit
1*: Position detective circuit
error
3*: Motor lock error
4*: Motor current detection
C*: TH sensor error
D*: TH sensor error
E*: Inverter DC voltage error
(outdoor unit fan)
ALT
Outdoor fan IPDU error
IPDU
P26
P26
01: Comp. 1 side
02: Comp. 2 side
03: Comp. 3 side
ALT
G-TR short protection error
IPDU
Содержание MML-AP0074NH-E