Monitoring function of remote controller switch
When using the remote controller (Model Name: RBC-AMT3
2UL
), the following monitoring
function can be utilized.
Calling of display
<Contents>
The temperature of each sensor of the remote controller, indoor unit and outdoor unit and the operating
status can be checked by calling the service monitor mode from the remote controller.
<Procedure>
1
Push
TEST
+
CL
buttons simultaneously for 4 seconds or more to call up the service monitor mode.
The service monitor goes on and firstly the temperature of the CODE No.
is displayed.
1 2 3 4
Returns to normal display
<Operation procedure>
2
4
1
3
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
2
Push
TEMP.
button to change CODE No.
to the CODE No. to be monitored.
For display code, refer to the following table.
3
Push
UNIT LOUVER
(left side button) button to change
The sensor temperature of indoor unit or
outdoor unit in its refrigerant line and the
operating status are monitored.
4
Push
TEST
button to return the status to the
normal display.
to item to be monitored.
SVM-13085.indb 50
SVM-13085.indb 50
12/24/13 10:56 AM
12/24/13 10:56 AM
<RBC-AMT
***
>
<RBC-AMS5*E-UL>
The sensor temperature or operational status of
indoor unit, outdoor unit, or remote controller can be
monitored.
Monitor function
Code
00
Data
0024
Return
Procedure
1
Push the [
MENU] button to display
the menu screen.
2
Push and hold the [
MENU] button
and the [
] button at the same time
to display the “Field setting menu”.
→
Push and hold the buttons for more than 4
seconds.
3
Push the [
] / [
] button to
select “4. Monitor function” on the “Field
setting menu” screen, then push the “
S
et
Set” [
F2
F2] button.
→
] button to
Push the [
] / [
select the code to check data.
4
Push the [
CANCEL] button to return
to the “Field setting menu” screen.
- 48 -