CODE No.
ON/OFF
TEMP
TIMER SET
FAN
MODE
SAVE
VENT
SWING/FIX
UNIT LOUVER
RESET TEST
FILTER
UNIT No.
R.C No.
3
6
5 1
4 2
<Fig. 1 RBC-AMT32
UL
>
TIME
SET CL
button is pressed, the indoor unit Nos. in the group control operation are displayed in
Every time when the
Step 2
order.
(The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values.)
Specify the indoor unit No.with its P.C. board replaced to the P.C. board for indoor unit servicing.
(You cannot perform this operation if is displayed.)
Step 3 Select the CODE No. (DN) can be selected by pressing the / button
for the temperature setting.
▪ Set the indoor unit type and capacity.
The factory-set values shall be written to the EEPROM by changing the type and capacity.
1. Set the CODE No. (DN) to . (without change)
2. Select the type by pressing / buttons for the timer setting.
(For example, High wall type is set to “0008” Refer to table 2 on page 4.)
3. Press
button. (The operation completes if the setting data is displayed.)
4.
buttons for the
5.
Change the CODE No. (DN) to by pressing /
temperature setting.
Select the capacity by pressing / buttons for the timer setting.
(For example, 024 Type is set to “0011”. Refer to table 2 on page 4.)
6. Press button. (The setting completes if the setting data are displayed.)
7.
button to return to the normal stop status.
Press the
(It takes approx. 1 min until the remote control operation is available again.)
SET
SET
The CODE No. (DN) are ranged from to
Write the on-site setting data to the EEPROM, such as address setting, etc. Perform the steps 1 and 2 above again.
Change the CODE No. (DN) to by pressing / buttons for the temperature setting.
(this is the setting for the filter sign lighting time.)
Check the setting data displayed at this time with the setting data put down in [1] (on page 1).
*
1. If the setting data is different, modify the setting data by pressing / buttons for the timer setting to the
data put down in [1].
The operation completes if the setting data is displayed.
2. If the data is the same, proceed to next step.
Change the CODE No. (DN) by pressing / buttons for the temperature setting.
As described above, check the setting data and modify to the data put down in [1].
Repeat the steps 6 and 7.
button to return to the normal stop status.
(It takes approx. 1 min until the remote control operation is available again.)
after modifying the data wrongly and pressing
.The CODE No. (DN) is not limited to be serial No. Even
button, it is possible to return to the data before modification
button if the CODE No. (DN) is not changed.
After the setting completes, press
SET
by pressing
CL
<Fig.2 EEPROM layout diagram>
The EEPROM (IC503) is attached to the IC socket. When
detaching the EEPROM, use a tweezers, etc. Be sure to
attach the EEPROM by fitting its direction as shown in the
figure.
* Do not bend the IC lead when replacing.
EEPROM
<Fig.2>
IC socket
Cut out
Cut out
EEPROM
IC501
2
N
SW01
1
O
L01
T01
2
N
SW02
1
O
C08
R04
DB01
IC503
J02
J01
UNIT LOUVER
(It takes approx. 1 min until the remote control operation is available again.)
TEST
TEST
- 115 -