Duct design
Duct design
1
In order to prevent short circuits, design
the duct work so that the intake and
discharge openings are not adjacent to
each other.
2
The indoor unit does not have a built-in air
¿
lter.
Always install the air
¿
lter (Local procure) in
a location that permits easy maintenance,
such as behind the intake grille. (If no air
¿
lter is installed, dust will collect in the
heat exchanger, which may cause the air
conditioner to fail or to leak.)
<Overview of duct connection>
NOTE
Parts except air conditioner unit are to be locally
procured.
Canvas joint
Canvas joint
Silencer
chamber
Air inlet
Air
¿
lter
Silencer
chamber
Air supply
port
Check port
(Air Conditioner)
Arrangement
(Unit: mm)
Referring to the following dimensions, manufacture duct at the local site.
(Thickness of plate : 0.8 mm)