– 28 –
Procedure
1
2
3
4
5
Operation contents
Push [TEST] button for 4 seconds or more.
[TEST] is displayed at the display part and
the mode enters in TEST mode.
Push [ON/OFF] button.
Change the mode from [COOL] to [HEAT] using [MODE] button.
• Do not use [MODE] button for other mode except
[COOL]/[HEAT] modes.
• The temperature cannot be adjusted during test run.
• The error detection is performed as usual.
After test run, push [ON/OFF] button to stop the operation.
(Display on the display part is same to that in Procedure
1
.)
Push [TEST] button to clear the TEST mode.
([TEST] display in the display part disappears and
status becomes the normal stop status.)
8-2. Functions at test run
Cooling/Heating test run check
The test run for cooling/heating can be performed from either indoor remote controller or outdoor interface
P.C. board.
1. Start/Finish operation of test run
~
~
~
~
~
Test run from indoor remote controller
Wired remote controller: Refer to the below item of “Test run” of the wired remote controller.
Wireless remote controller: Refer to the next page item of “Test run” of the wireless remote controller.
In case of wired remote controller
Note)
The test run returns to the normal operation after 60 minutes.
<RBC-AMT32UL>
1,
5
2,
4
3
TEMP.
ON / OFF
SET
TIME
TEST
FILTER
RESET
CL
SAVE
SWING/FIX
VENT
UNIT LOUVER
TIMER SET
MODE
FAN
TEST
TEST
All manuals and user guides at all-guides.com