Power supply specifications

Power supply cord and communication wires are procured locally.

For the power supply specifications, follow to the table below.

If capacity is little, it is dangerous because overheat or seizure may be caused.

For specifications of the power capacity of the outdoor unit and the power supply wires, refer to the Installation
Manual attached to the outdoor unit.

Indoor unit power supply

 (*1)

• For the power supply of the indoor unit, prepare the exclusive power supply separated from that of the outdoor unit.

• Arrange the power supply, earth leakage breaker, and main switch of the indoor unit connected to the same

outdoor unit so that they are commonly used.

• Power supply cord specification : Cable 3-core 2.5mm², in conformity with Design 60245 IEC 57.

Indoor/Outdoor inter-unit wiring, Central controller wiring

 (*2) (*3)

• 2-core with polarity wires are used for the Indoor/Outdoor inter-unit wiring and Central controller wiring.

• To prevent noise trouble, use 2-core shield wire.

• The length of the communication line means the total length of the inter-unit wire length between indoor and

outdoor units added with the central control system wire length.

Remote controller wiring

 (*4)

• 2-core with non-polarity wire is used for wiring of the remote controller wiring

and group remote controllers wiring.

Remote controller inter-unit wiring

Indoor unit

Remote

controller

Indoor unit

L1

L2

Ln

(Max. 8 units)

Indoor unit

Indoor unit

Remote 
controller 
wiring

Twist wire: 0.5mm

2

 to 2.0mm

2

 × 2

Total wire length of remote controller
wiring and remote controller inter-unit
wiring = L + L1 + L2 + … Ln

In case of wired type only

In case of wireless type included

Remote controller wiring, remote
controller inter-unit wiring

CAUTION

The remote controller wire
(Communication line) and
AC220–240V wires cannot be
parallel to contact each other and
cannot be stored in the same
conduits. If doing so, a trouble
may be caused on the control
system due to noise, etc.

Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln

Up to 500m

Up to 400m

Up to 200m

Power supply (*1)

Communication line

220–240V 

~

  50Hz, 220V 

~

  60Hz

Twist wire : 2.0 mm²

Twist wire : 3.5 mm²

(Up to 1000m) Twist wire : 1.25 mm²
(Up to 2000m) Twist wire : 2.0

0

 mm²

(Up to 1000m) Twist wire : 1.25 mm²
(Up to 2000m) Twist wire : 2.0

0

 mm²

Twist wire : 0.5 to 2.0 mm²

Power supply

Power supply wiring

Indoor/Outdoor inter-unit wiring (*2)
(2 cables)

Central control line wiring (*3)
(2 cables)

Remote controller wiring (*4)
(2 cables)

Below 20m

Below 50m

Wire size

Wire size

Wire size

Power supply switch/Earth leakage breaker or power supply wiring/fuse rating for
indoor units should be selected by the accummulated total current values of the indoor units.

6

ELECTRIC WORK

Содержание MMD- AP0091BH

Страница 1: ...R MULTI SYSTEM AIR CONDITIONER For commercial use Not accessible to the general public Indoor Unit Concealed Duct Type MMD AP0071BH AP0091BH AP0121BH MMD AP0151BH AP0181BH AP0241BH MMD AP0271BH AP0301BH AP0361BH MMD AP0481BH AP0561BH ...

Страница 2: ...l and hand over it ADOPTION OF NEW REFRIGERANT This Air Conditioner is a new type which adopts a new refrigerant HFC R410A instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer CONTENTS Accessory parts and Parts to be procured locally 3 1 PRECAUTIONS FOR SAFETY 4 2 SELECTION OF INSTALLATION PLACE 5 3 INSTALLATION OF INDOOR UNIT 7 4 DRAIN PIPING WORK 9 5 REF...

Страница 3: ...different from those of the conventional refrigerant Take out the flare nut attached to the indoor unit of the air conditioner and use it Part name Installation Manual Heat insulating pipe Washer Q ty 1 2 8 Shape This manual M10 Ø34 Usage Be sure to hand over to customers For heat insulation of pipe connecting section For hanging up unit Part name Standard wired remote controller Q ty 1 Shape Usag...

Страница 4: ...connect the Appliance from Main Power Supply This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm WARNING Ask an authorized dealer or qualified installation professional to install maintain the air conditioner Inappropriate installation may result in water leakage electric shock or fire Turn off the main power supply switch or br...

Страница 5: ...ECTION OF INSTALLATION PLACE WARNING Install the air conditioner at enough strong place to withstand the weight of the unit If the strength is not enough the unit may fall down resulting in injury Install the air conditioner at a height 2 5m or more from the floor If you insert your hands or others directly into the unit while the air conditioner operates it is dangerous because you may contact wi...

Страница 6: ...tenance for electric parts such as fan motor is unavailable Reference Dewing test conditions Indoor side 27 C dry bulb temperature 24 C wet bulb temperature Air volume Low air volume operation time 4 hours Installation under high humidity atmosphere In some cases including the rainy season especially inside of the ceiling may become high humidity atmosphere dew point temperature 23 C or higher 1 I...

Страница 7: ...ess remote controller can be installed in the same room Within 8m 3 INSTALLATION OF INDOOR UNIT WARNING Install the air conditioner certainly to sufficiently withstand the weight If the strength is insufficient the unit may fall down resulting in human injury Perform a specified installation work to guard against strong wind or earthquake An incomplete installation can cause accidents by the units...

Страница 8: ... units central control system wire and remote controller wire up to the position where pipes and wires are connected before hanged up the indoor unit The hanging bolts and nuts will be procured locally Anchor bolt Blade type bracket Slide type bracket Pipe hanging anchor bolt Reinforcing steel Hanging bolt Hanging bolt Support angle Installation of hanging bolt Use M10 hanging bolts 4 pcs to be lo...

Страница 9: ...welling or trap on the piping It may cause an abnormal sound For length of the traversing drain pipe restrict to 20m or less In case of a long pipe provide support brackets with interval of 1 5 to 2m in order to prevent waving Set the collective piping as shown in the right figure Do not mount an air purge pipe otherwise drain water spouts out resulted in water leak The hard vinyl chloride pipe ca...

Страница 10: ... the float switch connector to the original position CN34 of P C board and then set the electric parts box as before Thermal insulating process After check of draining apply thermal insulation surely to the pipe connecting part Give taping without clearance to the striking section of the main unit with thermal insulator at local site Rising up 550mm or less 100mm or less Indoor unit 220 240V 50Hz ...

Страница 11: ...al and dimensions Piping material Model MMD AP Pipe size mm Gas side Liquid side Phosphor deoxidization joint less pipe for air conditioner 0071BH to 0121BH 0151BH to 0181BH 0241BH to 0561BH Ø9 5 Ø12 7 Ø15 9 Ø6 4 Ø6 4 Ø9 5 0 0 4 A Use a clean and new pipe and check that impurity such as dust oil moisture etc does not adhere in the pipe Pipe Forming End Positioning Flaring 1 Cut the pipe with a pip...

Страница 12: ...ting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak but also a trouble of the refrigerating cycle REQUIREMENT If an excessive torque is applied the nut may crack depending on the installation conditions Airtight test Air purge etc For airtight test air purge addition of refrigerant and gas leak check follow...

Страница 13: ...ing Otherwise the system will be failed Perform the electric wiring so that it does not come to contact with the high temperature part of the pipe The coating may melt resulted in an accident After connecting wires to the terminal blocks provide a trap and fix wires with the wire clamp Store the refrigerant piping line and control wiring line in the same line Do not turn on the power of the indoor...

Страница 14: ...g of the remote controller wiring and group remote controllers wiring Remote controller inter unit wiring Indoor unit Remote controller Indoor unit L1 L2 Ln Max 8 units Indoor unit Indoor unit Remote controller wiring Twist wire 0 5mm2 to 2 0mm2 2 Total wire length of remote controller wiring and remote controller inter unit wiring L L1 L2 Ln In case of wired type only In case of wireless type inc...

Страница 15: ... The cover of the electric parts box remains hanged to the hinge Tighten the screws of the terminal block and fix the wires with cord clamp attached to the electric parts box Do not apply tension to the connecting section of the terminal block Be sure to set a loop for the connecting wire of the storing part of the indoor unit electric parts otherwise the electric parts box cannot be drawn out in ...

Страница 16: ...roller wiring of indoor unit A B Approx 200mm W White B Black W B Remote controller wire Local procure Wire from remote controller unit or sensor Connecting part Remote controller unit or sensor part Wire from remote controller or sensor Remote controller wiring Wire joint Header unit Follower unit Earth leakage breaker Earth leakage breaker Switch Earth Open Earth Outdoor power supply 3 phase 380...

Страница 17: ...at the displayed item code is 10 If the item code indicates other than 10 push button to erase the display and then retry the operation from the first step For some time after button has been pushed the operation of the remote controller cannot be accepted In a group control the firstly displayed indoor unit No becomes the center unit The display changes according to the indoor unit model Every pu...

Страница 18: ...a Standard At shipment 70Pa 1 High static pressure 1 100Pa 2 High static pressure 2 20Pa High static pressure 1 65Pa for Model AP0481BH AP0561BH 2 90Pa for Model AP0481BH AP0561BH In case of remote controller less Group control For setup to the high ceiling there is selecting method by exchanging the short plugs on the indoor microcomputer P C board as shown in the following table other than selec...

Страница 19: ...asic operation procedure 1 2 3 4 5 6 For the item code in Procedure 3 specify 06 For the set data in Procedure 4 select the setup data of shift value of detection temperature to be set up from the table below Setup data 0000 0001 0002 0003 0004 0005 0006 Detection temp shift value No shift 1 C 2 C At shipment from factory 3 C 4 C 5 C 6 C Group control In a group control a remote controller can con...

Страница 20: ...owing items 1 Using 500V megger check there is 1MΩ or more between the terminal block of the power supply and the earth If 1MΩ or less is detected do not run the unit 2 Check that all the valves of the outdoor unit are fully opened Never push the electromagnetic contactor to carry out a forced test operation It is very dangerous because a protective device does not work How to execute test operati...

Страница 21: ...peration has finished reset necessarily the leak breaker of the indoor unit Procedure 1 2 3 4 Description Remove a small screw which fixes the nameplate of the receiver unit Remove the nameplate of the sensor section by inserting a minus screwdriver etc into the notch at the bottom of the plate and set the Dip switch to TEST RUN ON Execute a test operation with button on the wireless remote contro...

Страница 22: ... 1 2 3 Description When pushing SET and buttons simultaneously for 4 seconds or more the right display appears If Service Check is displayed the mode enters in the error history mode 01 Order of error history is displayed in CODE No window Check Code is displayed in CHECK window Indoor unit address in which an error occurred is displayed in UNIT No Every pushing buttons the error history stored in...

Страница 23: ...is nothing during automatic addressing Capacity over No of connected indoor units Communication error between indoor units Outdoor header units quantity error Other line connected during automatic address Sending error in communication between outdoor units Duplicated follower outdoor addresses Decrease of No of connected outdoor units Follower outdoor unit error IPDU communication error Judging d...

Страница 24: ...me Indoor TCJ sensor error Indoor TC2 sensor error Indoor TC1 sensor error TD1 sensor error TD2 sensor error TE1 sensor error TL sensor error TO sensor error Indoor TA sensor error TS1 sensor error TH sensor error Outdoor temp sensor miscabling TE TL Outdoor pressure sensor miscabling Pd Ps Ps sensor error Pd sensor error Indoor other error Indoor EEPROM error Compressor break down Magnet switch e...

Страница 25: ...oor overflow error Indoor fan motor error Outdoor liquid back detection error Gas leak detection Discharge temp TD2 error 4 way valve inverse error High pressure protective operation Outdoor fan IPDU error G TR short protection error Comp position detective circuit system error Other indoor unit error Group terminal unit error Error in indoor group AI NET communication system error Duplicated netw...

Страница 26: ... is operating Remote controller start button ON When the air conditioner stops and the error is cleared the check code display on the remote controller also disappears However if the error continues after stop of the operation the check code is immediately displayed with restarting AI NET WORK bus Indoor unit AI NET central control remote controller Main remote controller OC F10 Network adaptor Us...

Страница 27: ... Clogging of the air filter decreases cooling heating efficiency 3 After cleaning push display disappears Concealed Duct Type 1 Take out the air filter Push the extrusion of the air filter to inside and pull out it to take out the air filter 2 Cleaning with water or vacuum cleaner If dirt is heavy clean the air filter by tepid water with neutral detergent or water After cleaning with water dry the...

Страница 28: ... the number of high concentration buildings however the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space individual control energy conservation by curtailing heat and carrying power etc Most importantly the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air co...

Страница 29: ... 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to Applicable controls in this sheet Filter sign lighting time Filter sign lighting time Filter sign lighting time Filter sign lighting time Item code 01 Item code 01 Item code 01 Item code 01 o NO CHANGE o NO CHANGE o NO CHANGE o NO CHA...

Отзывы: