Installation space
(Unit: mm)
Reserve sufficient space required for installation or service work.
Filter cleaning sign term setting
The lighting term setup of the filter sign (Notification of filter cleaning) of the remote controller can be changed
according to the condition of installation.
For setup method, refer to “Filter sign setting” in the Applicable controls of this Manual.
100 or
more
Air discharge
Ceiling
25
A
25
25
00
or
mor
e
B
or more
70
o
r
mo
re
5 or
mor
e
275
Inspection opening (Ceiling opening)
Floor surface
Air discharge
100 or more
450
Check port
120
Service space
(B for maintenance of air filter)
B
Ceiling
25
50 or more
Inspection opening (Ceiling opening)
570
Air intake
Air intake
570
25
Ceiling
Inspection opening (Ceiling opening)
Air intake
570
25
Ceiling
Inspection opening (Ceiling opening)
300 or more
A
B
AP0056~AP0186
750
700
AP0246~AP0306
1050
500
AP0366~AP0566
1450
700
4
Installation
CAUTION
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering
cloth or other material to not damage the unit.
• To move the indoor unit, hold the hooking brackets (4 positions) only.
Do not apply force to the other parts (such as refrigerant pipe, drain pan, foamed parts, or resin parts).
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
• To install vibration isolation material to hanging bolts, confirm that it does not increase the unit vibration.
External dimensions
(Unit: mm)
Dimension
A
B
C
D
AP0056~AP0186
700
765
640
750
AP0246~AP0306
1000
1065
940
1050
AP0366~AP0566
1400
1465
1340
1450
1
180
275
C
L
750
0
5
0
5
355
345
236
22
25
570
43
187.5
131
415
13.5
Main unit dimension A
Hanging bolt pitch B
External dimensions of flange C
Access panel
Electrical
control box
D
345
o
r
mo
re
70
or more
Drain pan / Drain
pump check cover
Hanging bolt pitch 650
3. Installation to a place where inside of the ceiling is used for pathway to intake the fresh air
4. Installation to a kitchen
• In the above cases, additionally attach the heat insulator to all positions of the air conditioner, which come to
contact with the high-humidity atmosphere. In this case, arrange the side plate (Check port) so that it is easily
removed.
• Apply also a sufficient heat insulation to the duct and connecting part of the duct.
[Reference]
Condensation test conditions
Indoor side: 27 °C dry bulb temperature
24 °C wet bulb temperature
Air volume:
Low air volume, operation time 4 hours