MMD-AP0246BHP1-E1

MMD-AP0276BHP1-E1
MMD-AP0306BHP1-E1
MMD-AP0366BHP1-E1
MMD-AP0486BHP1-E1
MMD-AP0566BHP1-E1

Indoor Unit

Model name:

Concealed Duct Type

MMD-AP0056BHP1-E1

MMD-AP0096BHP1-E1  
MMD-AP0126BHP1-E1

MMD-AP0076BHP1-E1

MMD-AP0156BHP1-E1
MMD-AP0186BHP1-E1

AIR CONDITIONER (MULTI TYPE)

Installation Manual

English

For commercial use

Содержание MMD-AP0056BHP1-E1

Страница 1: ...HP1 E1 MMD AP0486BHP1 E1 MMD AP0566BHP1 E1 Indoor Unit Model name Concealed Duct Type MMD AP0056BHP1 E1 MMD AP0096BHP1 E1 MMD AP0126BHP1 E1 MMD AP0076BHP1 E1 MMD AP0156BHP1 E1 MMD AP0186BHP1 E1 AIR CONDITIONER MULTI TYPE Installation Manual English For commercial use ...

Страница 2: ...ng work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in ...

Страница 3: ...ap Repair of outdoor unit Gloves to provide protection for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might get...

Страница 4: ...he intake grille of the indoor unit to undertake work Wear protective gloves and safety work clothing during installation servicing and removal Do not touch the aluminium fin of the unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and then proceed Before opening the inspection opening set the circuit breake...

Страница 5: ...the specified installation work to guard against the possibility of high winds and earthquake If the air conditioner is not installed appropriately a unit may topple over or fall down causing an accident If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may generate Use forklift to carry in...

Страница 6: ...le in the places where the wire is extended may give rise to smoking and or a fire Electrical wiring work shall be conducted according to law and regulation in the community and installation manual Failure to do so may result in electrocution or short circuit Test run Before operating the air conditioner after having completed the work check that the electrical control box cover of the indoor unit...

Страница 7: ...ION New refrigerant air conditioner installation This air conditioner adopts the new HFC refrigerant R410A which does not destroy ozone layer The characteristics of R410A refrigerant are easy to absorb water oxidizing membrane or oil and its pressure is approx 1 6 times higher than that of refrigerant R22 Accompanied with the new refrigerant refrigerating oil has also been changed Therefore do not...

Страница 8: ...quipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditioner or noise may adversely affect the equipment s operation Locations where there is anything under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation from the indoor unit will drip pos...

Страница 9: ...ering cloth or other material to not damage the unit To move the indoor unit hold the hooking brackets 4 positions only Do not apply force to the other parts such as refrigerant pipe drain pan foamed parts or resin parts Carry the package by two or more persons and do not bundle it with plastic band at positions other than specified To install vibration isolation material to hanging bolts confirm ...

Страница 10: ...ge to confirm whether the unit is hang horizontally Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Washer M10 8 pieces New concrete slab Install the bolts with insert brackets or anchor bolts Steel flame structure Use existing angles or install new support angles Existing concrete slab Use a hole in anchors hole in plugs or a hole in bolts Rubber Anchor bolt Blade type bracket Slide t...

Страница 11: ...l go Fix it with hose band REQUIREMENT Mount the flexible drain hose using the hose band without using adhesive Pipe material Hard vinyl chloride pipe VP25 Nominal outer diameter Ø32 mm Insulator Foamed polyethylene foam thickness 10 mm or more 1 5 m to 2 m Support bracket Downward slope 1 100 or more Arched shape Trap Downward slope 1 100 or more Collective piping As long as possible Approx 10 cm...

Страница 12: ...y starts running Check whether the water is draining from the drain pipe connecting port and check that no water is leaking from the drain pipe After checking that the water drains and there are no water leaks turn off the power connect the float switch connector to its original location CN34 on the printed circuit board and return the electrical control box to its original position Supply water h...

Страница 13: ... tap 50 Pa High tap 30 Pa High tap 40 Pa 0 20 40 60 80 100 120 140 570 770 970 1170 1370 External static pressure Pa Air volume m3 h Standard air volume 1200m3 h Upper limit of external static pessure 120Pa Lower limit of external static pessure 120Pa High tap 80Pa Low tap 120Pa High tap 100Pa High tap 65Pa High tap 50Pa High tap 120Pa High tap 40Pa High tap 30Pa Standard filter pressure loss Stan...

Страница 14: ...00 100 100 100 100 100 100 100 100 100 254 975 37 5 37 5 27 27 960 235 2 100 100 100 100 100 100 100 100 100 100 100 254 27 27 37 5 37 5 1359 4 100 100 235 4 100 100 100 100 100 100 100 100 100 100 100 100 100 254 1375 27 27 37 5 37 5 1360 235 2 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 Under air intake Back air intake Under air intake Back air intake Under air intake Back air in...

Страница 15: ...nect the indoor unit pipe Use the tightening torque levels as listed in the following table Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas le...

Страница 16: ...core and inner insulator of power and system interconnection wires when peeling them Use the power cord and system interconnection wire of specified thickness type and protective devices required Do not connect 208 V 240 V power to the terminal blocks for control wiring Otherwise the system will fail Perform the electric wiring so that it does not come to contact with the high temperature part of ...

Страница 17: ...1 25 mm Up to 2000 m 2 0 mm Remote controller wiring remote controller inter unit wiring Wire size 0 5 mm to 2 0 mm Total wire length of remote controller wiring and remote controller inter unit wiring L L1 L2 Ln In case of wired type only Up to 500 m In case of wireless type included Up to 400 m m 0 0 2 o t p U n L 2 L 1 L g n i r i w t i n u r e t n i r e l l o r t n o c e t o m e r f o h t g n ...

Страница 18: ...icable controls REQUIREMENT When the air conditioner is used for the first time it will take some moments after the power has been turned on before the remote controller becomes available for operations This is normal and is not indicative of trouble Concerning the automatic addresses The automatic addresses are set up by performing operations on the outdoor interface circuit board While the autom...

Страница 19: ...essure of the duct to be connected To set up a tap change follow to the basic operation procedure 1 2 3 4 5 6 Specify 5d to the CODE No in procedure 3 For the SET DATA of procedure 4 select a SET DATA of the external static pressure to be set up from the following table The list above is when SW501 1 and SW501 2 is OFF If the setting is wrong P12 may appear indicating a fan motor error SET DATA Ex...

Страница 20: ...ATA Detection temperature shift value 0000 No shift 0001 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C SET DATA 0000 0001 Remotecontroller sensor Not used Factory default Used 10Test run Before test run Before turning on the power supply carry out the following procedure 1 By using 500 V megger check that resistance of 1 MΩ or more exists between the terminal block L to N and th...

Страница 21: ...r or opening the service panel After the test run reset the circuit breaker of the indoor unit TEMPORARY button 11Maintenance 1 Take out the air filter Slide and remove the filter as shown in the following figure WARNING When the first filter comes out without connected to the other one insert it once more to connect the two filters together and pull out them as connected Do not insert hands to ta...

Страница 22: ...ropriate measures when abnormal sound is generated Filter Indoor Dust dirt breakage Wash the filter with water when it is contaminated Replace it when it is damaged Fan Indoor Vibration balance Dust dirt appearance Replace the fan when vibration or balance is terrible Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them w...

Страница 23: ...troller E03 97 Communication error between indoor unit and remote controller Detected at indoor unit side Indoor unit E04 04 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received 04 Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected a...

Страница 24: ...1 Comp 1 side 02 Comp 2 side 03 Comp 3 side 1d Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 17 Current detect circuit system error IPDU H04 H04 44 Comp 1 case thermo operation I F H05 H05 TD1 sensor miswiring I F H06 H06 20 Low pressure protective operation I F H07 H07 d7 Oil level down detective protection I F H08 H08 01 TK1 sensor error 02 TK2 sensor error 03...

Страница 25: ...2 side 03 Comp 3 side AF ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp I F P07 P07 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side IC ALT Heat sink overheat error IPDU I F P09 P09 Detected heat storage address 47 ALT No heat storage unit water error Heat storage unit P10 P10 Detected indoor unit address...

Страница 26: ... 2 Comp 3 Fan Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display AI NET central control display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending error in TCC LINK central control device TCC LINK C06 Receiving error in TCC LINK central control device TCC LINK C12 Batch ala...

Страница 27: ...MiNi SMMS series Complies with the provisions of the Machinery Directive Directive 2006 42 EC and the regulations transposing into national law Declaration of incorporation of partly completed machinery Must not be put into service until the final machinery into which it is to be incorporated has been declared in conformity with the provisions of this Directive where appropriate MMD AP0096BHP1 E1 ...

Страница 28: ...tioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The standards for minim...

Страница 29: ... 5 0005 F STATIC 6 0006 External static pressure CODE NO 5d F NO CHANGE F STANDARD 0000 F STATIC 1 0001 F STATIC 2 0002 F STATIC 3 0003 F STATIC 4 0004 F STATIC 5 0005 F STATIC 6 0006 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting ...

Страница 30: ...1116950191 144 9 Moo 5 Bangokdi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand ...