117
18
Trial Operation
Service Support Function
Function to start/stop (ON/OFF) indoor unit from outdoor unit
A function to start/stop the following indoor units by switch operation on the interface
P.C. board is provided.
NOTE:
This start/stop function is only to send the mode signals such as stop/operation mode, etc. from
outdoor unit to indoor unit.
No.
Function
Outline
Clear setup
(1)
Trial cooling
The modes of all the connected indoor units [Setup]
operation
are collectively changed to trial cooling
Push SW04 for 2 seconds or more under
operation modes.
condition of SW01 “2”, SW02 “5”,
SW03 “1”.
NOTE:
Control operation is the same as that of
[Clear]
normal trial operation from the remote
Returns SW01, SW02 and SW03 to “1”.
controller.
(2)
Collective
All the connected indoor units are operated
[Setup]
operation
collectively.
Push SW04 for 2 seconds or more under
condition of SW01 “2”, SW02 “7”,
NOTE:
SW03 “1”.
Operation contents match the setup on the
remote controller.
[Clear]
Returns SW01, SW02 and SW03 to “1”.
Collective
All the connected indoor units are stopped
[Setup]
stop
collectively.
Push SW05 for 2 seconds or more under
condition of SW01 “2”, SW02 “7”,
SW03 “1”.
[Clear]
Returns SW01, SW02 and SW03 to “1”.
(3)
Individual
The specified indoor unit is operated.
[Setup]
operation
To operate SW01 “16”, SW02 and SW03
NOTE:
Set to the indoor address No. (1 to 40),
Operation contents match the setup on the
and push SW04 for 2 seconds or more.
remote controller.
Other indoor units stay as they are.
[Clear]
Returns SW01, SW02 and SW03 to “1”.
Individual
The specified indoor unit is stopped.
[Setup]
stop
Setting SW01 “16”, SW02 and SW03 to the
NOTE:
address No. (1 to 40) of the indoor unit to
Other indoor units are as they are.
be operated, push SW05 for 2 seconds or
more.
[Clear]
Returns SW01, SW02 and SW03 to “1”.
Содержание MM-A0160HX
Страница 1: ...Service Manual Air Conditioner Multi Split Type System Modular Multi System HFCR407C A90 0130 ...
Страница 2: ......
Страница 123: ...124 19 Exploded Views and Service Parts Outdoor Units MM A0280HT MM A0280HX MM A0224HT MM A0224HX ...
Страница 133: ...134 20 Additional Literature and Contacts ...
Страница 134: ...135 20 Additional Literature and Contacts ...
Страница 135: ...TOSHIBA AIR CONDITIONING www toshiba aircon co uk MADE IN UK A90 0130 Revised April 2001 ...