– 2 –

LN INTERFACE

Installation Manual

EN

1

Precautions for safety

• Read these “Precautions for Safety” carefully before installation.
• The precautions described below include important items regarding safety. Observe them without fail.

Understand the following details (indications and symbols) before reading the body text, and follow the 
instructions.

• After the installation work has been completed, perform a test run to check for any problems. Explain how to use 

and maintain the unit to the customer.

• Ask customer to keep this Manual at accessible place for future reference.

Indication

Meaning of Indication

Text set off in this manner indicates that failure to adhere to the directions in the warning could result in 

serious bodily harm (*1) or loss of life if the product is handled improperly.

Text set off in this manner indicates that failure to adhere to the directions in the caution could result in 

serious bodily injury (*2) or damage (*3) to property if the product is handled improperly.

*1: Serious bodily harm indicates loss of eyesight, injury, burns, electric shock, bone fracture, poisoning, and other 

injuries which leave aftereffect and require hospitalization or long-term treatment as an outpatient.

*2: Bodily injury indicates injury, burns, electric shock, and other injuries which do not require hospitalization or long-

term treatment as an outpatient.

*3: Damage to property indicates damage extending to buildings, household effects, domestic livestock, and pets.

Symbols

Meaning of Symbols

" Indicates prohibited items.

The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic 

symbol.

" Indicates compulsory (mandatory) items.

The actual contents of the obligation indicated by a picture or text placed inside or next to the graphic 

symbol.

Ask an authorized dealer or qualified installation professional to install or reinstall this unit.

Inappropriate installation may result in electric shock or fire.

Electrical work must be performed by a qualified electrician in accordance with this installation 
manual. 
The work must satisfy all local, national and international regulations.

Inappropriate work may result in electric shock or fire.

Be sure to turn off all main power supply switches before starting any electrical work.

Failure to do so may result in electric shock.

Do not modify the unit.

A fire or an electric shock may occur.

Do not install this unit where flammable gas may leak.

If gas leaks and accumulates around the unit, it may cause a fire.

Perform wiring correctly in accordance with specified the current capacity.

Failure to do so may result in short-circuiting, overheating or fire.

Use predefined cable and connect them certainly. Keep the connecting terminal free from 
external force.

It may cause an exothermic or a fire.

WARNING

CAUTION

WARNING

CAUTION

2-EN

+00DE93429101_01EN.book  Page 2  Wednesday, October 26, 2011  6:41 PM

Содержание LonWorks TCB-IFLN642TLUL

Страница 1: ...LN INTERFACE Installation Manual Model name TCB IFLN642TLUL Toshiba 00DE93429101_01EN book Page 1 Wednesday October 26 2011 6 41 PM ...

Страница 2: ...bles communication cables earth wires 5 6 Setting 7 7 Test run 9 and LON are registered trademarks of Echelon Corporation in United States and other countries Thank you very much for purchasing this TOSHIBA Carrier LN interface Please read this manual carefully beforehand for proper installation of the LN interface 1 EN 00DE93429101_01EN book Page 1 Wednesday October 26 2011 6 41 PM ...

Страница 3: ... an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets Symbols Meaning of Symbols Indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol Indicates compulsory mandatory items The actual contents of the obligation indicated by a picture or text ...

Страница 4: ...of operating status room temperature various settings etc One LN interface has a capacity to control indoor units of up to 64 units A free topology FT X1 transceiver is used as the LONWORKS transceiver also communicatable with FTT 10A Specifications External view Unit inch mm Name LN interface Model TCB IFLN642TLUL Power supply 120 VAC 60 Hz Power consumption 5 W Number of connectable indoor units...

Страница 5: ... space and maintenance space A side space for connecting through cable inlets and an upper space for maintenance must be reserved before installation The other sides can be adjacent to surrounding objects No Item Quantity Remarks 1 LN interface 1 2 Installation Manual 1 3 Screw 4 5 32 x 0 47 M4 x 12 mm tapping screws No Line Description 1 For TCC LINK Type 2 core shield wires Wire size AWG16 1 25 ...

Страница 6: ... N SW2 SW4 LED7 LED8 SW1 SW6 SW5 SW8 LED1 LED2 LED3 LED4 LED5 LED6 SW3 1 2 3 4 Power supply 120 VAC 60 Hz Air conditioner LONWORKS system Connect the earth wire to the earth terminal of the chassis The TCC LINK communication cable must be earthed on the air conditioner Do not connect the shield wire to the terminal block It should be open and insulated Connect the power supply cable and earth wire...

Страница 7: ...lated Connect the shield wire of the LONWORKS communication cable to the earth on the upper system side TCC LINK FG L N U1 U2 LON SW5 SW2 SW1 L ON W ORKS U2 U1 U4 U3 U2 U1 U2 U1 U2 U1 U4 U3 U2 U1 U4 U3 TCC LINK main bus Outdoor unit Building management system by other company Do not connect the shield wire to the terminal block Set maximum 1 of the indoor unit central control address with SW1 and ...

Страница 8: ...ddress differs from the number of connected indoor units In this case set the maximum of the central control address according to the table below Note The system works normally when the set value is larger than the maximum However it will result in communication loss Indoor unit central control address SW1 SW2 Indoor unit central control address SW1 SW2 Indoor unit central control address SW1 SW2 ...

Страница 9: ...sed to set TCC LINK terminator resistor The TCC LINK terminator resistor is set on the air conditioner side and is not set here Set SW5 to Open SW6 Reset switch When changing the setting of the number of connected indoor units with SW1 and SW2 push this reset switch after setting to read the set value SW8 Service pin for LONWORKS system Used for Commissioning with the upper LONWORKS system SW5 TCC...

Страница 10: ...W2 setting Example When checking communication status of indoor unit of central control address 25 Set bit 2 of SW3 to ON SW1 to 1 and SW2 to 8 Indication of TCC LINK communication status LED4 and LED 5 show communication status of the indoor unit selected by SW1 and SW2 End of TCC LINK communication status check Re set SW1 and SW2 to the number of connected indoor units and set bit2 of SW3 to OFF...

Страница 11: ...hts temporarily when TCC LINK is busy during auto address setting of an air conditioner etc Communication restarts soon LED5 TEST Test indicator Used in the test mode LED6 UP LINK LONWORKS communication status indicator Blinks during LONWORKS communication LED7 RESET Reset indicator Lights when reset operation is performed LED8 SERVICE LONWORKS indicator Ask the manufacturer of the upper system fo...

Страница 12: ...DE93429101 Toshiba 00DE93429101_01EN book Page 13 Wednesday October 26 2011 6 41 PM ...

Отзывы: