Limitation of use

 

Safety precaution

 

 

Never use this unit with any device other than TOSVERT VF-FS1 series inverters. Doing so may 
cause an accident. 

„

 

Handling in general

 

 

Danger

 

 

Never 

Disassemble

 

  Never disassemble, modify or repair the product. 

Disassembling the product may cause electric shocks, fire or injuries. 
For repairs, call your sales/repair agency.

 

 

Do not open the front cover on the inverter while the inverter power is on. 
It may lead to electric shocks. 

  Do not remove this option from VF-FS1 while the power is on. 

 

It may lead to electric shocks. 

 Do not put or insert foreign objects such as waste cable, bars or wires into the product. 

Prohibited 

It may lead to electric shocks or fire. 

 Do not splash water over the product, and do not wipe the body with a wet cloth. 

It may lead to electric shocks or fire.

 

 Turn off the power immediately in case of any abnormalities such as smoke, smell or 

abnormal noise. 
Neglect of these conditions may lead to fire. 

 

For repairs, call your sales/repair agency. 

 Do not touch the sharp portions (such as leads of parts on the board, the corner of 

board, or etc.) on this option

 

It may lead to injuries. 

Mandatory 

 

Warning

 

 

This option is an electrostatic discharge sensitive device. Handle it, where the 
environment is protected against electrostatic electricity. 
Otherwise, permanent damage to device will result.

 

 

Mandatory 

„

 

Transportation and installation

 

 

Danger

 

 

Do not apply a dropping shock or other physical shocks.   
Otherwise, damage or malfunction will result. 

 

Do not install or operate the inverter if it is damaged or any part of it is missing.   

 

Operating a defective inverter may lead to electric shocks or fire. 

Prohibited 

For repairs, call your sales/repair agency. 

 

Do not put any flammable material near the product. 
It may catch fire due to the product sparking in the case of a malfunction.

 

 Use this product under the environmental conditions prescribed in the instruction 

manual.  
Usage it under any other conditions may result in malfunction.   

 An emergency stop device must be installed that fits with system specifications 

  (e.g. shut off input power then engage mechanical brake).   
Operation cannot be stopped immediately by the inverter or this unit alone, thus risking 
an accident or injuries. 

 

Mandatory 

 Install this option into VF-FS1 and secure it by tightening the terminal board fixing 

screws to the specified torque. Otherwise, it may cause the product falling, the damage, 
or malfunctions.   

 When installing this option, do not touch its sharp portions such as leads of parts on the 

board, the corner of board or etc.

 

Doing so may result in injury.

 

 

 

- 2 - 

Содержание LONWORKS LIU007Z

Страница 1: ... is delivered to the end user of LONWORKS communication option 2 Read this manual before installing or operating the LONWORKS communication option Keep it in a safe place for reference 3 All information contained in this manual are subject to change without notice Please confirm the latest information on our web site www inverter co jp ...

Страница 2: ...injury 1 to people or that these errors may cause damage to physical property 2 1 Such things as injury burns or shock that will not require hospitalization or long periods of outpatient treatment 2 Physical property damage refers to wide ranging damage to assets and materials Meanings of symbols Marking Meaning of marking Indicates prohibition Do not do it What is prohibited will be described in ...

Страница 3: ...discharge sensitive device Handle it where the environment is protected against electrostatic electricity Otherwise permanent damage to device will result Mandatory Transportation and installation Danger Do not apply a dropping shock or other physical shocks Otherwise damage or malfunction will result Do not install or operate the inverter if it is damaged or any part of it is missing Operating a ...

Страница 4: ...ime f803 see the inverter instruction manual for details Receive heart beat timer See the VF FS1 LONWORKS Communication Function Manual for details Deactivated option unit may cause an accident if the Communication error trip function is not properly set up Make sure that the operation signals are STOP before clearing the inverter s fault The motor may suddenly start and that may result in injurie...

Страница 5: ...this instruction manual please keep it handy for future reference Echelon LONWORKS LonTalk Neuron LONMARK LONMARK Logo are the registered trademarks or the trademarks of Echelon Corporation in the USA and other countries LONMARK and LONMARK Logo are managed granted and used by LONMARK International under a license granted by Echelon Corporation Part numbering LIU 007 Z 0 Revision number Cable leng...

Страница 6: ...minals 7 3 Installation and Setup 8 3 1 Installation method 8 3 2 VF FS1 communication parameters 9 3 3 Network cable connection 9 3 4 Network configuration 10 3 5 Termination resistor 11 3 6 Wiring of a control terminal 11 4 Before making a service call 12 4 1 Display of service LED 12 4 2 Other problems 12 5 Specifications 13 6 Warranty 14 5 ...

Страница 7: ...ate Service switch only when a cover for the main circuit terminal is attached Otherwise it may lead to electric shocks Operate Service switch using the non conductive stick When it is operated with a conductive stick Otherwise it may lead to electric shocks 2 2 Use of RS485 communication port Serial communication 2 wire RS485 option can be used However while it is connected the internal communica...

Страница 8: ... SINK 820 VIB Multifunction programmable analog input with internal pull up resistor for PTC 0 to 10VDC input Using this terminal as PTC input set SW1 to PTC side and set the parameters f645 and f646 to proper value VIB 15k VIB P10 PTC 15k 3 3k CC Control circuit s equipotential terminal P24 24 VDC power supply output 24VDC 50mA P24 P24 PTC FLA FLB FLC Multifunctional programmable relay contact ou...

Страница 9: ...stall the LONWORKS communication option over the insulating sheet and secure it with the board fixing screw tightening torque of M3 tapping screw 0 7 to 0 8Nm 6 Stick the cabling label for LONWORKS communication option on the standard cabling label stuck on the reverse side of the VF FS1 front cover And stick the LONWORKS communication option nameplate near the standard nameplate Be careful not to...

Страница 10: ...s tripping an operating error power outage failure etc Deactivated option unit may cause an accident if the Communication error trip function is not properly set up 3 3 Network cable connection Connect the LONWORKS network cable to LONWORKS communication option as follows 1 Cable selection a twisted pair cable with shield Use Level 4 22 AWG cable for the network cable Recommended cable Manufacture...

Страница 11: ...opology total wire length is 1400m or less stub length is 3m or less Twisted pair cable with shield Host computer Router LIU007Z Terminal resistor 52 3ohm 1 8W Shield grounding resistor NETA NETB SHLD LIU007Z NETA NETB SHLD LIU007Z NETA NETB SHLD Terminal 1 Terminal 2 Connection image Network configuration is shown in the figures below This LONWORKS communication option has TP FT 10 channel type t...

Страница 12: ...ove the sheath of a cable about 7mm 6mm for FLA FLB FLC and G E from the end of cable Use a flat headed screwdriver with its blade 0 6mm in thickness and 3 5mm in width Screw tightening torque for the terminal block screws should be 0 5 to 0 6Nm N B Keep the control signal cables 20cm or more separate from the power cables to prevent from malfunctioning due to electromagnetic noise N B Provide an ...

Страница 13: ...ame indication appears after resetting the power it needs to be repaired 5 LED blinks every 1 second This is a normal action of the Unconfigured device If the device is not Unconfigured Internal application program is broken It needs to be repaired 6 LED momentarily turns ON then continues to be OFF When the program is in the condition of Configured status LED momentarily turns ON when the inverte...

Страница 14: ... Power supply output 24V 50mA Current limit function DC Network side Item Specification Notes Transceiver TP FT 10 type 78kbps Channel type Free topology transceiver ANSI EIA CEA 709 3 Communication signal 2 wires plus shield NETA SHLD NETB Transmission distance Between devices 400m at maximum When recommended cable is used Free topology Total cable length 500m at maximum Level 4 22AWG Total cable...

Страница 15: ...r damage the repair cost shall be borne by the customer even within the warranty period i Failure or damage caused by improper or incorrect use or handling or unauthorized repair or modification of the inverter ii Failure or damage caused by the unit falling or an accident during transportation after the purchase iii Failure or damage caused by fire salty water or wind corrosive gas earthquake sto...

Отзывы: