HX7+ ASD Installation and Operation Manual
85
ST Input Terminal Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the
ST
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
ST
terminal to 1 of the 68 possible
Direct Access Number — F113
Parameter Type —
Selection List
Factory Default —
Standby
Changeable During Run —
No
RES Input Terminal Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the
RES
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
RES
terminal to 1 of the 68 possible
Direct Access Number — F114
Parameter Type —
Selection List
Factory Default —
Reset
Changeable During Run —
No
S1 Input Terminal Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the
S1
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
S1
terminal to 1 of the 68 possible
Direct Access Number — F115
Parameter Type —
Selection List
Factory Default —
Preset Speed Cmd #1
Changeable During Run —
No
S2 Input Terminal Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the
S2
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
S2
terminal to 1 of the 68 possible
Direct Access Number — F116
Parameter Type —
Selection List
Factory Default —
Preset Speed Cmd #2
Changeable During Run —
No
S3 Input Terminal Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the
S3
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
S3
terminal to 1 of the 68 possible
Direct Access Number — F117
Parameter Type —
Selection List
Factory Default —
Preset Speed Cmd #3
Changeable During Run —
No
S4 Input Terminal Assignment
Program
Terminal Selection
Input Terminals
This parameter selects the functionality of the
S4
input terminal.
In addition, the input terminal must be specified as
Normally Open
or
Normally Closed
.
This parameter sets the programmable
S4
terminal to 1 of the 68 possible
Direct Access Number — F118
Parameter Type —
Selection List
Factory Default —
Emergency Off
Changeable During Run —
No
Содержание HX7+ ASD
Страница 1: ...HX7 ASD Install Op Manual TOSHIBA HX7 ASD INSTALLATION OPERATION MANUAL DN 67017 001 February 2014 ...
Страница 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Страница 219: ...210 HX7 ASD Installation and Operation Manual Figure 27 66 200 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 220: ...HX7 ASD Installation and Operation Manual 211 Figure 28 260 518 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 221: ...212 HX7 ASD Installation and Operation Manual Figure 29 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 222: ...HX7 ASD Installation and Operation Manual 213 Figure 30 1200 1500 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 223: ...214 HX7 ASD Installation and Operation Manual Figure 31 66 200 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 224: ...HX7 ASD Installation and Operation Manual 215 Figure 32 260 518 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 225: ...216 HX7 ASD Installation and Operation Manual Figure 33 518 1000 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 226: ...HX7 ASD Installation and Operation Manual 217 Figure 34 1200 1500 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Страница 228: ...HX7 ASD Installation and Operation Manual 219 Figure 36 260 518 kVA Sine Wave NEMA 1 Enclosure ...
Страница 229: ...220 HX7 ASD Installation and Operation Manual Figure 37 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 230: ...HX7 ASD Installation and Operation Manual 221 Figure 38 932 1500 kVA Sine Wave NEMA 1 Enclosure ...
Страница 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Страница 232: ...HX7 ASD Installation and Operation Manual 223 Figure 40 260 518 kVA Sine Wave NEMA 3R Enclosure ...
Страница 233: ...224 HX7 ASD Installation and Operation Manual Figure 41 518 1000 kVA Sine Wave NEMA 3R Enclosure ...
Страница 234: ...HX7 ASD Installation and Operation Manual 225 Figure 42 932 1500 kVA Sine Wave NEMA 3R Enclosure ...
Страница 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Страница 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Страница 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Страница 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...