172
HX7+ ASD Installation and Operation Manual
Cumulative Run Timer Alarm Setting
Program
Protection
Cumulative Run Timer
This parameter sets a run-time value that, once exceeded, closes a contact. The
output signal may be used to control external equipment or used to engage a
brake.
Note:
The time displayed is 1/10th of the actual time (0.1 hr. = 1.0 hr.).
Direct Access Number — F621
Parameter Type —
Numerical
Factory Default —
175.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 999.9
Units — Hours (X 100)
Abnormal Speed Detection Filter Time
Program
Protection
Abnormal Speed
This parameter sets the time that an over-speed condition must exist to cause a
trip.
Direct Access Number — F622
Parameter Type —
Numerical
Factory Default —
10.0
Changeable During Run —
No
Minimum — 0.01
Maximum — 100.0
Units — Seconds
Over-Speed Detection Frequency Range
Program
Protection
Abnormal Speed
This parameter sets the upper level of the
Base Frequency
range that, once
exceeded, will cause an
Overspeed Detected
alert.
Direct Access Number — F623
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 30.0
Units — Hz
Speed Drop Detection Frequency Range
Program
Protection
Abnormal Speed
This parameter sets the lower level of the
Base Frequency
range that, once
exceeded, will cause a
Speed Drop Detected
alert.
Direct Access Number — F624
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Over-Voltage Stall Level (fast)
Program
Protection
Stall
This parameter sets the upper DC bus voltage threshold that, once exceeded,
will cause an
Over-Voltage Stall
. An
Over-Voltage Stall
increases the output
frequency of the drive during deceleration for a specified time in an attempt to
prevent an
Over-Voltage Trip
.
If the over-voltage condition persists for over 250 µS, an
Over-Voltage Trip
will be incurred.
Note:
This feature may increase deceleration times.
Direct Access Number — F625
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
Yes
Minimum — 50.00
Maximum — 250.0
Units — %
Содержание HX7+ ASD
Страница 1: ...HX7 ASD Install Op Manual TOSHIBA HX7 ASD INSTALLATION OPERATION MANUAL DN 67017 001 February 2014 ...
Страница 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Страница 219: ...210 HX7 ASD Installation and Operation Manual Figure 27 66 200 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 220: ...HX7 ASD Installation and Operation Manual 211 Figure 28 260 518 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 221: ...212 HX7 ASD Installation and Operation Manual Figure 29 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 222: ...HX7 ASD Installation and Operation Manual 213 Figure 30 1200 1500 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 223: ...214 HX7 ASD Installation and Operation Manual Figure 31 66 200 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 224: ...HX7 ASD Installation and Operation Manual 215 Figure 32 260 518 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 225: ...216 HX7 ASD Installation and Operation Manual Figure 33 518 1000 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 226: ...HX7 ASD Installation and Operation Manual 217 Figure 34 1200 1500 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Страница 228: ...HX7 ASD Installation and Operation Manual 219 Figure 36 260 518 kVA Sine Wave NEMA 1 Enclosure ...
Страница 229: ...220 HX7 ASD Installation and Operation Manual Figure 37 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 230: ...HX7 ASD Installation and Operation Manual 221 Figure 38 932 1500 kVA Sine Wave NEMA 1 Enclosure ...
Страница 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Страница 232: ...HX7 ASD Installation and Operation Manual 223 Figure 40 260 518 kVA Sine Wave NEMA 3R Enclosure ...
Страница 233: ...224 HX7 ASD Installation and Operation Manual Figure 41 518 1000 kVA Sine Wave NEMA 3R Enclosure ...
Страница 234: ...HX7 ASD Installation and Operation Manual 225 Figure 42 932 1500 kVA Sine Wave NEMA 3R Enclosure ...
Страница 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Страница 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Страница 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Страница 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...