– 12 –
Hydro Unit
Installation Manual
Electrical supply/cable specifications
▼
Wiring specifications
▼
Wiring specifications (control line)
Description
Model name
HWT-
POWER
SUPPLY
Maximum
current
Installation
fuse rating
Power wire
Connection destination
Outdoor
Unit
power
Power
input
1101H(R)W-E
220-240 V ~
50 Hz
20.3 A
25 A
2.5 mm² or more
,
801H(R)W-E
220-240 V ~
50 Hz
20.3 A
25 A
2.5 mm² or more
601HW-E
220-240 V ~
50 Hz
14.6 A
16 A
1.5 mm² or more
401HW-E
220-240 V ~
50 Hz
14.6 A
16 A
1.5 mm² or more
Hydro
inlet
heater
power
Power
input for
backup
heater
1101XWHM3W-E 220-240 V ~
50 Hz
13 A
16 A
1.5 mm² or more
,
TB03
1101XWHT6W-E
380-415 V 3N~
50 Hz
13 A(13 A x 2P) 16 A
1.5 mm² or more
, ,
,
1101XWHT9W-E
380-415 V 3N~
50 Hz
13 A(13 A x 3P) 16 A
1.5 mm² or more
601XWHM3W-E
220-240 V ~
50 Hz
13 A
16 A
1.5 mm² or more
,
601XWHT6W-E
380-415 V 3N~
50 Hz
13 A(13 A x 2P) 16 A
1.5 mm² or more
, ,
,
Power input for cylinder
heater
220-240 V ~
50 Hz
12 A
16 A
1.5 mm² or more
,
TB02
Outdoor-Hydro Unit
Connection
1.5 mm² or more
,
,
TB01
Hydro -Cylinder
Connection
1.5 mm² or more
,
TB02
Description
Line spec
Maximum
current
Maximum length Power wire
Connection
destination
3-way valve control
2 line or 3 line
100 mA
12 m
0.75 mm² or more
,
,
(CN23)
2-way valve control
2 line
100 mA
12 m
0.75 mm² or more
,
(CN23)
Mixing valve control
3 line
100 mA
12 m
0.75 mm² or more
,
,
(CN22)
2-zone thermo sensor
2 line
100 mA
5 m
0.75 mm² or more
,
(CN20)
Cylinder thermo sensor
2+GND(shielded
wire)
100 mA
5 m
0.75 mm² or more
,
(CN20)
Second remote controller
2 line
50 mA
50 m
0.5 mm² or more
(TB04)
Group control (total)
2 line
50 mA
50 m
0.5 mm² or more
(TB04)
Open protocol interface
2 line
100 mA
50 m
0.5 mm² or more
(TB04)
▼
Control parts specifications
▼
Output line specifications
▼
Input line specifications
CAUTION
Earthing arrangements
The Hydro Unit and related equipment must be earthed in accordance with your local and national electrical regulations.
It is essential that the equipment is earthed to prevent the electric shock and damage to the equipment.
Power
Maximum current
Type
Motorized 3-way valve
(for hot water)
AC 230 V 100 mA
Default: 2-wire spring return valve or 3 wire SPST valve
Note: 3 wire SPDT valve can be used by changing DN 6B4.
Motorized 2-way valve
(for cooling)
AC 230 V 100 mA
spring return type (normally open)
Motorized mixing valve
(for 2-zone)
AC 230 V 100 mA
Default: Drive time = 60sec to 90°
Note: 3 wire SPST or SPDT valves, with drive times between
30 and 240 seconds, can be used. Valve drive time can be
changed using DN 0C
Description
Output
Maximum
current
Max
voltage
Maximum
length
External pump No.1
AC230 V
1 A
–
12 m
External boost heater
AC230 V
1 A
–
12 m
Output as required when outdoor air
temperature is -20 °C or less
Digital outputs from CN22
Non-voltage
contacts
0.5 A
AC230 V
12 m
1 A
DC24 V
12 m
Description
Input
Maximum length
Digital inputs to CN21
Non-voltage
12 m
23-EN
24-EN