Installation Manual
Electrical connection to Hydro Unit for
backup heater
• Remove the front cover and the electrical box cover
from the Hydro Unit.
• The Hydro Unit power cable must be sized in
accordance with refer to “Electrical supply/cable
specifications”.
• Connect the Hydro Unit power cable to Terminal 03
as shown below.
• Ensure the Hydro Unit power cable is secured using
the cable clamp fitted in the electrical box.
• Ensure the Hydro Unit power cable connection
terminals are tight.
Outdoor Unit to Hydro Unit electrical
connection
▼
Fig.7-16
• Ensure electrical circuits are isolated before
commencing work.
• The Outdoor Unit to Hydro Unit interconnecting
cable must be sized in accordance with refer to
“Electrical supply/cable specifications”.
• Connect the Outdoor Unit to Hydro Unit
interconnecting cable as shown in the diagram
above.
• Ensure the Outdoor Unit to Hydro Unit
interconnecting cable is secured using the cable
clamp fitted in the electrical box.
• Ensure the Outdoor Unit to Hydro Unit
interconnecting cable connection terminals are tight.
L N
L1 L2 L3 N
TB03
TB03
▼
Fig.7-15
Leakage
breaker
30 mA
Leakage
breaker
30 mA
Input power
220-240 V
50 Hz
Backup heater
220-240 V ~ type
(3 kW type)
Backup heater
380-415 V 3N~
type
(6,9 kW type)
Input power
380-415 V
3N ~ 50 Hz
3kW type
TB03
1
2
3
4
L
N
6kW, 9kW type
TB03
1
2
3
4
L3
L2
L1
N
N
L
1
3
2
1
3
2
TB
01
Leakage
breaker
30 mA
Input
power
220-240 V
~ 50 Hz
Outdoor Unit
Hydro Unit
Outdoor Unit
Electrical connection for external booster
heater
CAUTION
• The maximum current available from the
booster heater output is 1
A. Do not connect
the booster heater directly to CN23 on the
Hydro Unit. A separate contactor, supplied
locally, must be used to supply the booster
heater.
• The booster heater can be installed only for room
heating and cannot be used for hot water supply.
The booster heater is an external heater, supplied
locally, used to assist the Hydro Unit during low
ambient conditions.
• The AC230 V 1 A output from the Hydro Unit must only
be used to energize an external contactor. (Supplied
locally)
• The output from the Hydro Unit is only enabled when
the outdoor air temperature is less than -20°C.(*)
• Ensure the external booster heater is installed and set
up in accordance with all Local, National and
International regulations.
(*) For HWT-110, it is less than -25°C.
• Connect the external booster heater to the Hydro
Unit in accordance with the diagram shown below.
• Connect the coil, of the field supplied contactor, to
terminals 5 & 6 on CN23. The contactor will energize
in the event of low ambient conditions.
• A separate dedicated electrical supply must be used
for the external booster heater. This must be
connected through the contacts on the field supplied
contactor.
▼
Fig.7-17
To cable channel for power
cables (Refer to “Fig.6-01(29)”)
To cable channel for Low voltage
cables (Refer to “Fig.6-01(30)”)
Power supply & CDU
communication
Digital
output
Second
controller
Digital input
230 V AC output
Power supply for the
backup heater
1
2
3
4
5
6
7
8
9
CN23
Booster Heater
27-EN
28-EN
Содержание HWT-1101F21MM3W-E