[F04] Error TD sensor failure
[F06] Error TE sensor failure
[F07] Error TL sensor failure
Correct TD sensor
connection
Replace TD sensor
No
No
TD sensor
connector (CN603) is
connected
Yes
TD sensor
resistance characteristic
is normal
Yes
Start
Replace water heat exchange control board
(Refer to Characteristic table on page 113)
Correct TE sensor
connection
Replace TE sensor
No
No
TE sensor
connector (CN601) is
connected
Yes
TE sensor
resistance characteristic
is normal
Yes
Start
Replace water heat exchange control board
(Refer to Characteristic table on page 113)
Correct TL sensor
connection
Replace TL sensor
No
No
TL sensor
connector (CN604) is
connected
Yes
TL sensor
resistance characteristic
is normal
Yes
Start
Replace water heat exchange control board
(Refer to Characteristic table on page 113)